3.4 -
MINIMUM CLARANCE FOR
SERVICING
Observe minimum distance of the boiler
TOP of the boiler:
24''
FRONT of the boiler: 12" + 24" = 36"
RIGHT side:
12''
LEFTside:
12''
BACK of the boiler:
12'
Maintain an installation clearance from combustible construc-
tion from hot water piping of at least 1" (25 mm).
12''
300 mm
16
(600 mm)
(900 mm)
(300 mm)
(300 mm)
(300 mm)
12''
300 mm
3.5 -
The boiler must be installed in accordance with the directions
indicated in the most recent Standards and legislations
regarding boiler rooms, installation of heating and hot water
systems, boiler ventilation, chimney's capable of discharging
the products of combustion of condensing boilers and any
other applicable requirement.
The boiler will be placed on a flat and sufficiently strong base-
ment,, with dimensions not smaller than the ones of the boiler.
After installation the boiler will result perfectly horizontal and
very stable ( in order to reduce vibrations and noise).
Installation
When choosing the installation place, the following items
- To grant an easy access to the boiler components in order
- The floor should not be of flammable material.
- If the floor is flammable an insulation material, with the
12''
24''
300 mm
610 mm
LOCATION OF BOILER INSIDE A
BOILER ROOM
have to be considered:
to facilitate the ordinary and extraordinary service opera-
tions.
capacity to withstand to the fire for at least 120 min should
be placed between the boiler and the floor and will protru-
de boiler basement of 19'' (0,5 m) all around.
24''
610 mm
Operating
space