11. Configuration errors

Error N.
Parameters
1
C1-C15 different from Screw1 or
Screw2
C16 = Btz or Frsc
2
One of C1-C15 parameters=
Screw1 or Screw2
C16 = SPo
3
One of C1-C15 parameters
configured as StP. Don't
configure any C1-C15
parameter as compressor.
4
One of C1-C15 parameters =
Frq1 after CPR1;
One of C1-C15 parameters =
Frq2 after CPR2
5
One of C1-C15 parameters =
Frq1F after FAN1; One of C1-
C15 parameters = Frq2F after
FAN2
6
One of C1-C15 parameters =
Screw1 or Screw2 followed by
more than 3 stp
C16 = Btz or Frsc
12. Mounting & installation
The instruments are suitable only for internal use. They are din rail mounted.
The ambient operating temperature range is between 0÷60°C.
Avoid locations subject to heavy vibration, corrosive gases or excessive dirt. The same applies to
the probes. Ensure ventilation around the instrument.
1592021021 XC1008-1011-1015D GB A5 r.1.5A 12.10.2009
Alarm description
Compressors configuration alarm.
Set properly par. C16
Compressors configuration alarm.
Set properly par. C16
Presence valve without compressor
Compressor before inverter: check C1-C15
parameters
or
More than one relay set as inverter: check
C1-C15 parameters.
or
One relay set as frequency compressors
and none analog output set: check C1-
C15 parameters and: 1Q2, 2Q1, 3Q2,
4Q1.
Fan before inverter: check C1-C15
parameters.
or
More than one relay set as inverter: check
C1-C15 parameters.
or
One relay set as fan inverter and no analog
output set: check C1-C15 parameters
and: 1Q2, 2Q1, 3Q2, 4Q1.
Number of wrong compressor steps: check
C1-C15 parameters.
XC1008-1011-1015D
Action
Machine stop (all relays
configured as compr. or
fans OFF)
Machine stop (all relays
configured as compr. or
fans OFF)
Machine stop (all relays
configured as compr. or
fans OFF)
Machine stop (all relays
configured as compr. or
fans OFF)
Machine stop (all relays
configured as compr. or
fans OFF)
Machine stop (all relays
configured as compr. or
fans OFF)
53/66