Code
Description
LAC1
Minimum
Suction pressure
(LAC)
pressure
or temperature
(temperature)
lower than
alarm
SETC1-AC3
compressors
(SETC2 –AC6)
for circuit 1
value
(2)
LAF1
Minimum
Condensing
(LAF2
pressure
pressure or
(temperature)
temperature
alarm fans
lower than
section for
SETF1-AF1
circuit 1 (2)
(SETF2 –AF9)
value
HAC1
Maximum
Suction pressure
(HAC2
pressure
or temperature
(temperature)
higher than
alarm
SETC1+AC4
compressors
(SETC2 +AC7)
for circuit 1
value
(2)
HAF1
Maximum
Condensing
(HAF2
pressure
pressure or
(temperature)
temperature
alarm fans
higher than
section for
SETF1+AF2
circuit 1 (2)
(SETF2 +AF10)
value
LL1(LL
Liquid level
Proper digital
2)
alarm for
input enabled
circuit 1 (2)
Clock
Clock failure
Problem on RTC
failure
alarm
board
Set
Clock data
The clock back
clock
lost
up battery is
exhausted
SEr1÷S
Compressors
A compressor
Er15
maintenance
has worked for
alarm
the time set in
the AC10
parameter
1592021021 XC1008-1011-1015D GB A5 r.1.5A 12.10.2009
Cause
Action
signalling only
signalling only
signalling only
It depends on
parameter AF4
(AF12)
signalling only
signalling only
With this alarm the
activation by RTC of
the reduced set point
and the alarm log are
not available.
signalling only
With this alarm
the activation by
RTC of the
reduced set point
and the alarm log
are not available.
signalling only
-
Reset
Automatically: as soon as the pressure or
temperature reaches the SETC1-AC3 (SETC2 –
AC6) + differential value.
(differential = 0.3bar or 1°C)
Automatically: as soon as the pressure or
temperature reaches the (SETF1-AF1 (SETF2 –
AF9) + differential) value.
(differential = 0.3bar or 1°C)
Automatically: as soon as the pressure or
temperature reaches the (SETC1-AC4 (SETC2 –
AC7) - differential) value.
(differential = 0.3bar or 1°C)
Automatically: as soon as the pressure or
temperature reaches the SETF1+AF2 (SETF2
+AF10) - differential value.
(differential = 0.3bar or 1°C)
Automatically as soon as the input is disabled
Manually: it is necessary to replace the RTC
board.
Manually: set the data and the time
Manually: reset the running hour of the
compressor
(see par. 4.5)