6.1.8 Compressor Action (CP1-CP8)
CP1
Regulation band width for compressors- circuit
1÷50°F; 10÷1000 KPA) The band is symmetrical compared to the target set point, with extremes:
SETC1+(CP1)/2 ... SETC1-(CP1)/2. The measurement unit depends on the C45 par.
NOTE: If the circuit 1 has 1 relay set as a frequency compressor (Frq1), the 1Q19 parameter is
used instead of the CP1 parameter: regulation band width that is added to the set point 1.
CP2
Minimum compressor set point - circuit 1 (AI2 ÷ SETC1 bar, PSI or KPA; -50.0 ÷ SETC1 °C; -58.0
÷ SETC1 °F). The measurement unit depends on C45 parameter. It sets the minimum value that can
be used for the compressor set point, to prevent the end user from setting incorrect values.
CP3
Maximum compressor set point - circuit 1 (SETC1÷AI3 bar/PSI/KPA; SETC1÷150.0°C;
SETC1÷302°F)
The measurement unit depends on C45 parameter. It sets the maximum acceptable value for
compressor set point.
CP4
Compressor energy saving value - circuit 1 (-20.00÷20.00bar; -50.0÷50.0 °C; -300÷300 PSI; -
90÷90 °F; -2000÷2000KPA) this value is add to the compressor set point when the energy saving is
enabled.
CP5
Regulation band width for compressors - circuit
1÷50°F; 10÷1000 KPA). The band is symmetrical compared to the target set point, with extremes:
SETC2+(CP5)/2 ... SETC2-(CP1)2. The measurement unit depends on the C43 par.
NOTE: If the circuit 1 has 1 relay set as a frequency compressor (Frq2), the 2Q18 parameter is
used instead of the CP5 parameter: regulation band width that is added to the set point 2.
CP6
Minimum compressor set point - circuit 2 (AI5 ÷ SETC2 bar or PSI o KPA; -50.0 ÷ SETC2 °C; -
58.0 ÷ SETC2 °F).
value that can be used for the compressor set point, to prevent the end user from setting incorrect
values.
CP7
Maximum compressor set point - circuit 2 (SETC2÷AI6 bar/PSI/KPA; SETC2÷150.0°C;
SETC2÷302°F)
The measurement unit depends on C45 parameter. It sets the maximum acceptable value for
compressor set point.
CP8
Compressor energy saving value - circuit 2 (-20.00÷20.00bar; -50.0÷50.0 °C; -300÷300 PSI; -
90÷90 °F) this value is add to the compressor set point when the energy saving is enabled.
6.1.9 Safety Compressors (CP9-CP19)
CP9
Minimum time between 2 following switching ON of the same compressor (0÷255 min).
CP10
Minimum time between the switching off of a compressor and the following switching on.
(0÷255min).
Note: usually CP9 is greater than CP10
CP11
Time delay between the insertion of two different compressors (0 ÷ 99.5 min; res. 1sec)
CP12
Time delay between switching off of two different compressors (0 ÷ 99.5 min; res. 1sec)
CP13
Minimum time load on (0 ÷ 99.5 min; res. 1sec)
CP14
Maximum time load on (0 ÷ 24 h; with 0 this function is disabled.) If a compressor keeps staying on
for the CP14 time, it's switched off and it can restart after the CP10 standard time or after the CP15
time with frequency compressor (Frq1 or Frq2).
CP15
Minimum time a frequency compressor (CP1..CP15 =Frq1 or Frq2) stays off after CP14 time
(0÷255 min)
CP16
CP11 delay enabled also for the first call. If enabled, the triggering of the step is delayed for a
"CP11" time, respect to the call.
no = "CP11" not enabled;
yES="CP11" enabled
CP17
CP12 delay enabled also for the first off. If enabled, the triggering of the step is delayed for a
"CP12" time, respect to the call.
no = "CP12" not enabled;
yES="CP12" enabled
CP18
Output delay at power on (0 ÷ 255 sec)
CP19
Booster function enabled:
no = compressors of 2 circuits work independently
yES = if at least one compressor of the circuit 1 (BT) is ON, also one compressor of the circuit 2
(TN) is enabled, independently from the pressure of the circuit 2. This ensures that the gas coming
from the circuit 1 is suct by the compressors of the circuit 2.
1592021021 XC1008-1011-1015D GB A5 r.1.5A 12.10.2009
The measurement unit depends on C45 parameter. It sets the minimum
1 (0.10÷10.00 bar; 0.1÷25.0°C, 1÷80PSI,
2 (0.10÷10.00 bar; 0.1÷25.0°C, 1÷80PSI,
XC1008-1011-1015D
31/66

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Xc1011dXc1015dVgc810

Table of Contents