g
3.1
TRANSPORT
Forklift
Crane
Fig. 3.1-1 UPS cabinets moving
3.1.1 Dimensions and weight
D
W
Fig. 3.1.1-1 UPS cabinet dimensions
UPS rating
SG Series 10 kVA
SG Series 20 kVA
SG Series 30 kVA
SG Series 40 kVA
P.S.: Weights including the 5th harmonic filter.
OPM_SGS_ISG_10K_40K_0US_V010.doc
3 INSTALLATION
Dimensions SG Series 10, 20, 30 and 40 kVA
H
Weight SG Series 10, 20, 30 and 40 kVA
UPS without battery
Floor loading
Weight
lbs / kg
lbs/sq.ft - kg/m
735 / 333
763 / 346
970 / 440
1,147 / 520
11/45
Transport UPS only in upright position!
The UPS is packaged on a pallet suitable for
handling with a forklift.
Pay attention to the center of gravity.
The UPS must be moved in upright position.
Do not tilt cabinets more than +/- 10° during
handling.
Move the UPS in it's original package to the
final destination site.
Do not stack other packages on top:
This could damage the UPS.
If the UPS must be lifted by crane, use suitable
lifting straps and spreader bars.
Note of the center of gravity marked on the
package.
Check
for
elevator loading capacity.
(W x D x H)
26.78 x 31.50 x 70.90 inches
680 x 800 x 1,800 mm
Weight
2
lbs / kg
126 / 613
1,121 / 508
131 / 637
1,169 / 530
166 / 809
–
196 / 956
–
Installation Guide SG Series 10, 20, 30 & 40 kVA
sufficient
floor
and
UPS with battery
Floor loading
lbs/sq.ft - kg/m
192 / 934
200 / 975
–
–
GE
2