GE Digital Energy SG Series Installation Manual page 22

Uninterruptible power supply 10, 20, 30 and 40 kva
Hide thumbs Also See for Digital Energy SG Series:
Table of Contents

Advertisement

g
Refer to torque specifications table for torque requirements.
SG Series 10 kVA
SG Series 20 kVA
SG Series 30 kVA
SG Series 40 kVA
OPM_SGS_ISG_10K_40K_0US_V010.doc
WIRING
Wire sizing according to
NEC Section 210-20 (a)
Use 75°C (167°C) copper wire
Wiring requirements:
AC INPUT RECTIFIER:
AC INPUT BYPASS:
AC OUTPUT:
DC INPUT:
Maximum cable diameter that terminals can accept.
Rectifier Input Bypass Input
3 AWG
3 AWG
3 AWG
3 AWG
1 AWG
1 AWG
1 AWG
1 AWG
22/45
Table 310-16
3-Phase, 3 wire plus Ground
3-Phase, 4 wire plus Ground
3-Phase, 4 wire plus Ground
2 wire (positive and negative) plus Ground
DC Input
AC Output
3 AWG
3 AWG
3 AWG
3 AWG
1 AWG
1 AWG
1 AWG
1 AWG
Installation Guide SG Series 10, 20, 30 & 40 kVA
GE
GND
3 AWG
3 AWG
1 AWG
1 AWG

Hide quick links:

Advertisement