Introduction; Safety Rules; Transport / Storage; Installation - GE Match lite 500 User Manual

Table of Contents

Advertisement

g
1.1

Introduction

The GE (General Electric) Digital Energy Match lite UPS, an uninterruptible power supply, protects
your equipment from all forms of power interference, including complete power failures.
1.2

Safety Rules

-
CAUTION:
outlets may be electrically live, even when the UPS is disconnected from the mains.
-
The UPS contains potentially hazardous voltages. Do not open the UPS, there are no
user serviceable parts inside.
-
Apart from battery replacement, all maintenance and service work should be performed
by qualified service personnel.
-
Always isolate the UPS from the mains during battery replacement.
1.3

Transport / Storage

-
No liability can be accepted for any transport damage when the equipment is shipped in non-
original packaging.
-
Before storing, charge the batteries for at least 24 hours.
Store the UPS in a dry location, storage temperature must be within -20 +45 !C. If the unit is
-
stored for a period exceeding 3 months, optimal battery lifetime is obtained if the storage
temperature does not exceed 25!C. Be sure that the UPS is switched off, and that no cable is
connected to the interface port.
-
If the unit is stored for a period exceeding 3 months, the batteries must be recharged periodically.
Connect the unit to a wall outlet for a period of approx. 48 hours, minimum every 3 months.
The shipping box contains a Match lite UPS, a power cord, a computer interface cable and this manual.
After unpacking, inspect the UPS for damage. If you find any damage please immediately notify the
carrier and place of purchase.
IMPORTANT:
Before making any connection and switching on the Match lite UPS, please check the following
conditions:
"
your mains supply is 220 - 240 Volts and 50 or 60 Hz, and
"
the total power demand of the connected equipment does not exceed the rated output power of
the Match lite UPS (indicated on the rear panel).
2.1

Installation Rules

-
The UPS is intended to be used in normal domestic and office situations.
-
Protect the UPS, according to the wiring rules, with a 16A D-type fuse.
-
The UPS must be powered from a single phase grounded wall outlet. Do not use extension
cords.
-
Avoid locations that are excessively humid, near water, near heat sources or in direct sunlight.
-
The ambient temperature should not exceed 40!C. Optimal battery lifetime is obtained if the
ambient temperature does not exceed 30!C.
-
It is important that ventilation air can move freely around and through the unit. Do not block the air
vents.
-
Do not plug appliances such as electric heaters, toasters and vacuum cleaners into the UPS. The
UPS output can be used only for electronic loads such as computers and telecommunications
equipment.
-
Be careful when connecting laser printers: be sure that the demanded power does not exceed the
capacity of the UPS.
OPM_MAE_LTE_500_XXX_1GB_V040
1 - Introduction
RISK OF ELECTRICAL SHOCK. The UPS contains batteries. The appliance

2 - Installation

2
GE Digital Energy
Match lite 500: user manual 4.0 (GB)