INSTALLATION

3.1

TRANSPORT

Forklift
Crane
Fig. 3.1-1 UPS cabinets moving

3.1.1 Dimensions and weight

D
W
Fig. 3.1.1-1 UPS cabinet dimensions
UPS rating
SG Series 50 kVA
SG Series 80 kVA
P.S.: Weight including the 5th harmonic filter and EMI filters.
Modifications reserved
OPM_SGS_ISG_50K_80K_0US_V040.doc
The UPS is packaged on a pallet suitable for handling with
a forklift.
Pay attention to the center of gravity.
The UPS must be moved in upright position.
Do not tilt cabinets more than +/- 10° during handling.
Move the UPS in it's original package to the final
destination site.
Do not stack other packages on top: This could damage
the UPS.
If the UPS must be lifted by crane, use suitable lifting straps
and spreader bars.
Note of the center of gravity marked on the package.
Take all necessary precautions to avoid damage to the
cabinet while hoisting the UPS.
H
Weight SG Series 50 & 80 kVA
Weight
lbs / kg
1,306 / 592
1,491 / 676
Transport UPS only in upright position!
NOTE !
Check for sufficient floor and elevator
loading capacity.
Dimensions SG Series 50 & 80 kVA
(W x D x H)
31.50 x 31.50 x 70.90 inches
800 x 800 x 1,800 mm
Floor loading
lbs/sq.ft / kg/m
2
190 / 925
217 / 1,057
Page 10/38
Installation Guide SG Series 50 & 80 kVA