HEATING PERFORMANCE DATA
MODEL: GSH101203AC / AR120
65
60
MBh
125700.0 119000.0 112000.0 104700.0
Delta T
34506.0
32666.8
30745.2
KW
9.58
9.40
AMPS
33.3
31.0
COP
3840.54
3706.53
3557.68
EER
13123.1
12665.2
12156.6
HI PR
189
182
LO PR
67
62
High pressure is measured at the suction service valve ( the larger valve).
Low pressure is measured at the gauge port connection.
Calculations are based on nominal CFM and 70 °F indoor dry bulb.
*Note: Shaded area is AHRI Rating Conditions at 47° outdoor ambient temperature
All data based upon listed indoor dry bulb temperature. .00 inches exter-
nal static pressure on coil of outdoor section. Indoor air cubic feet per
minute (CFM) as listed in the Performance Data Sheets:
If conditions vary from this, results will change as follows:
1.
As indoor dry bulb temperatures increase, a slight increase will
occur in indoor air temperature drop (Delta T). Low and high side
pressures and power will not change.
2.
As indoor CFM decreases, a slight increase will occur in indoor
temperature drop (Delta T). A slight decrease will occur in low and
high side pressures and power.
EXPANDED PERFORMANCE DATA
55
50
47
45
96900.0
100000.0
28741.3
27451.1
26600.1
9.21
9.03
8.85
8.93
29.1
27.4
26.5
26.0
3393.08
3279.04
3205.15
11594.2
11204.5
10952.0
175
167
163
160
58
53
50
48
Outdoor Ambient Temperature
40
35
30
25
90000.0
83000.0
74.8
69.0
24706.0
22784.4
20.5
18.9
8.67
8.49
9.48
9.26
24.6
23.4
22.5
21.6
3037.22
2861.28
2.31
2.18
10378.2
9777.0
7.9
7.4
154
148
141
135
45
40
36
32
PERFORMANCE TEST
A properly operating unit should be within plus or minus 2 degrees of
the subcooling value shown in the Heat Pump Specifications.
A properly operating unit should be within plus or minus 3 degrees of
the typical (Delta T) value shown.
A properly operating unit should be within plus or minus 7 PSIG of the HI
PR shown.
A properly operating unit should be within plus or minus 3 PSIG of the LO
PR shown.
A properly operating unit should be within plus or minus 3 Amps of the
typical value shown.
GSH101203AC
HEATING OPERATION
20
17
15
10
5
63.5
60.0
57.8
51.8
46.0
17.4
16.5
15.9
14.2
12.6
9.05
8.93
8.84
8.62
8.41
20.6
20.2
19.9
19.0
17.8
2.05
1.97
1.91
1.76
1.60
7.0
6.7
6.5
6.0
5.5
130
126
124
119
115
28
26
25
21
18
AMPS = Outdoor unit amps (comp.+fan)
0
-5
-10
40.1
34.2
28.0
11.0
9.4
7.7
8.20
7.98
7.77
16.9
15.7
14.3
1.43
1.25
1.06
4.9
4.3
3.6
110
106
103
15
14
11
KW = Total system power