Gsh130483A* / Aruf61-00*-1* / Aruf48601A: Heating Performance Data; Gsh13048-4A* / Aruf61-00*-1* / Aruf48601A: Heating Performance Data - Goodman GSH Series Service Instructions Manual

Split system air conditioners, split system heat pumps with r-22 refrigerant blowers, coils, & accessories
Table of Contents

Advertisement

HEATING PERFORMANCE DATA
MODEL: GSH130483A* / ARUF61-00*-1* / ARUF48601A*
65
60
55
MBh
54.1
51.2
48.2
Delta T
31.3
29.6
27.9
KW
3.71
3.64
3.57
AMPS
14.6
13.6
12.7
COP
4.26
4.11
3.95
EER
14.6
14.1
13.5
HI PR
224
215
206
LO PR
73
68
64
*Note: Shaded area is AHRI Rating Conditions at 47° outdoor ambient temperature.
High pressure is measured at the suction service valve ( the larger valve).
Low pressure is measured at the gauge port connection.
Calculations are based on nominal CFM and 70 °F indoor dry bulb.
MODEL: GSH13048-4A* / ARUF61-00*-1* / ARUF48601A*
65
60
55
MBh
54.1
51.2
48.2
Delta T
31.3
29.6
27.9
KW
3.87
3.78
3.70
AMPS
3.7
3.5
3.3
COP
4.09
3.96
3.81
EER
14.0
13.5
13.0
HI PR
180
172
166
LO PR
74
68
64
*Note: Shaded area is AHRI Rating Conditions at 47° outdoor ambient temperature.
High pressure is measured at the suction service valve ( the larger valve).
Low pressure is measured at the gauge port connection.
Calculations are based on nominal CFM and 70 °F indoor dry bulb.
70
EXPANDED PERFORMANCE DATA
Outdoor Ambient Temperature
50
47
45
40
43.0
45.0
41.7
38.7
26.1
24.9
24.1
22.4
3.45
3.50
3.42
3.35
12.0
11.6
11.3
10.7
3.77
3.64
3.56
3.38
12.9
12.4
12.2
11.5
197
193
189
182
58
55
53
49
EXPANDED PERFORMANCE DATA
Outdoor Ambient Temperature
50
47
45
40
45.0
43.0
41.7
38.7
26.1
24.9
24.1
22.4
3.61
3.56
3.52
3.44
3.1
3.0
3.0
2.8
3.65
3.53
3.46
3.29
12.5
12.1
11.8
11.2
158
155
152
146
59
56
53
49
35
30
25
20
35.7
33.6
31.1
28.6
20.7
19.5
18.0
16.5
3.28
3.34
3.26
3.19
10.2
9.8
9.3
8.9
3.18
2.95
2.79
2.63
10.9
10.1
9.5
9.0
174
167
159
153
44
39
35
31
35
30
25
20
35.7
43.6
40.3
37.1
20.7
25.2
23.3
21.4
3.36
3.29
3.20
3.12
2.7
2.6
2.5
2.4
3.11
3.88
3.68
3.48
10.6
13.3
12.6
11.9
140
134
128
123
44
39
35
31
HEATING OPERATION
17
15
10
5
27.0
26.0
23.3
20.7
15.6
15.0
13.5
12.0
3.14
3.11
3.04
2.96
8.7
8.6
8.2
7.7
2.51
2.44
2.25
2.04
8.6
8.4
7.7
7.0
149
147
141
136
29
28
23
20
AMPS = Outdoor unit amps (comp.+fan)
HEATING OPERATION
17
15
10
5
35.0
33.7
30.2
26.8
20.3
19.5
17.5
15.5
3.07
3.03
2.95
2.86
2.3
2.3
2.2
2.1
3.34
3.25
3.00
2.74
11.4
11.1
10.3
9.4
120
118
113
109
29
28
23
20
AMPS = Outdoor unit amps (comp.+fan)
KW = Total system power
GSH13
0
-5
-10
18.0
15.4
12.6
10.4
8.9
7.3
2.89
2.81
2.74
7.2
6.7
6.1
1.83
1.60
1.35
6.2
5.5
4.6
130
126
121
17
15
12
KW = Total system power
0
-5
-10
23.4
20.0
16.3
13.5
11.5
9.5
2.78
2.69
2.61
2.0
1.9
1.7
2.46
2.17
1.84
8.4
7.4
6.3
105
101
97
17
15
12

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents