Display/
settings
Q specifi cation
cos phi specifi cation
cos phi (P/Pn)
Nodes
Number of
nodes
1st node
2nd node
Q(U) characteristic
Action in this menu/meaning
Set the idle power Q (in % of device nominal power)
to a fi xed value.
Select the type of phase shift (under-excited (u) /
over-excited (o)).
Confi gure power factor.
If a power factor not equal to 1 is selected: Select
the type of phase shift (under-excited (u) /over-
excited (o))
Press "2" to retain the following mode > edit
characteristic.
Off ers the option of resetting or editing the nodes.
Press "1" to display all nodes in succession.
Press "1" to activate default characteristic and a
confi rmation message is shown.
By pressing "1" the individual nodes can be edited
This option defi nes the number of nodes that can be
defi ned in the subsequent menu.
•
Grid type for medium voltage and low voltage: up to
10 nodes defi nable
Increment P/Pn in % with key "2" and confi rm with
key "1".
Increment cos phi with key "2" and confi rm with key
"1".
If a power factor that is not equal to 1 is selected:
Select the type of phase shift (under-excited/over-
excited).
After running through all selected nodes all values
are saved by pressing "1" and then this characteristic
is checked for consistency.
In the event of an error, the characteristic that was
previously active is restored and the error message
"Characteristic invalid" appears.
You then have the option of correcting the
characteristic.
Specify the target voltage.
Specify slope.
Specify change time.