Kaco Powador 3200 Operating Instructions Manual page 43

Hide thumbs Also See for Powador 3200:
Table of Contents

Advertisement

C onfig ura tion an d O pe rat i on
Authorised electrician
Country-
Menu
spec. setting
level
1
2
3
3
1
2
3
3
All countries
1
2
3
3
DE-VDN
1
2
3
3
1
2
3
3
All countries
1
2
3
3
DE
NSp.
1
2
3
3
IT
CEI021
Operating Instructions Powador 3200-6600_EN
Display/
settings
Starting voltage
Grid monitoring
Activating
SYM bus
Activation P(f)
Internal power
limiting
Activate Powador
protect
Reactive power
setting
Action in this menu/meaning
The inverter begins grid feed as soon as this PV voltage
is present.
 Set the starting voltage.
Off ers the option of activating three-phase grid
monitoring. During this process, single-phase grid
monitoring is deactivated.
 Set grid monitoring.
The SYM bus must be activated in order to symmetrise
a group of inverters.
 Enter SYM bus CAN address (1-32)
 Set SYM bus phase (none, L1, L2, L3)
 Enter SYM bus asymmetry (< 4600 W (IT < 6000 W)
up to 100 W) setting in 100 W increments
 Activate SYM bus test (check settings for
plausibility)
 Off ers the option of activating active power
reduction in case of overfrequency.
 Activate P(f).
The power reduction function is password-protected.
Power is reduced in 10 W steps and is
limited to 50% of the nominal unit power.
 Enter the four-digit password using key "2".
 Set power limiting.
 Password protection can be re-activated.
Confi gures the support for grid shutdown by a Powador
protect connected to the digital input of the inverter.
↻ For Auto/On: A Powador protect is operating in
the photovoltaic system and is connected to the
inverter at the digital input/output.
 Auto: The inverter automatically detects a Powador-
protect integrated into the photovoltaic system.
 On: The digital signal of the Powador protect must
be pending at the digital input of the inverter for
the inverter to start with feed-in.
 Off : The inverter does not check whether a Powador
protect is integrated in the photovoltaic system.
The following control methods can be set. At least one
mode must be active.
 cos phi specifi cation
 cos phi(P/Pn)
 Q(U) characteristic
 Characteristic Q=f(U) - activate 5 nodes from value
pairs (Q1:U1 – Q5:U5).
 Characteristic Q=f(U) - activate two-state controller
with 4 fi xed
value pairs (Q:U).
Page 43