Z-Wave Configuration Command

Parameter Number
1 (0x01)
2 (0x02)
3 (0x03)
4 (0x04)
5 (0x05)
6 (0x06)
7 (0x07)
8 (0x08)
9 (0x09)
10 (0x0A)
Definitions
Swing
Differential
Set filter counter
Report filter counter
(read only)
Scale of temperature
Upper limit of set point (A)
Lower limit of set point (B)
Simple mode
Time format
Repeat basic set counter
Parameter value range
0x01 = 0.5 C / 1 F
0x02 = 1.0 C / 2 F (default)
0x03 = 1.5 C / 3 F
0x04 = 2.0 C / 4 F
0x01 = 0.5 C / 1 F
0x02 = 1.0 C / 2 F (default)
0x03 = 1.5 C / 3 F
0x04 = 2.0 C / 4 F
0x01F4 to 0x0FA0 (default = 0x01F4,
resolution = 0x0064)
(500 to 4000 hours;
resolution=100hrs )
0x0000 to 0x270F
(0 to 9999 hours)
o
0x00 = C
0x01 = F (default)
o
(A) available range:
o
Celsius ( C):
A = (B+2)min. ~ (37.0 C) max.
Fahrenheit ( F):
A = (B+4)min. ~ (99.0 F) max.
(default = 99.0 F)
(B) available range:
o
Celsius ( C): 5.0 C to 35.0 C
Fahrenheit ( F): 41.0 F to 95.0 F
0x00 = Disable (Normal mode)
0x01 = Enable (Simple mode),
default
0x00 = 24 hours
0x01 = 12 hours (am / pm), default
Value(X): 0x00, 0x03 to 0xFF
0X00 = Disable, default
Range from 0x03 to 0xFF =
3 minutes to 255 minutes
(Thermostat sends "Basic Set"
command to its association node
repeatedly in every X minutes)