Specifications; Xl Plus Series Specifications - Toshiba 1400XL Plus Series Operation Manual

Uninterruptible power system single phase - 2.4/3.6/6.0/8.0 kva plus
Table of Contents

Advertisement

TOSHIBA
5.0

Specifications

5.1

XL Plus Series Specifications

Input
Input harmonic distortion
Battery
Battery backup time when fully charged
with 0.7 power factor and 77° F (25° C)
Output
Output voltage regulation
Output voltage waveform
Rated load power factor
Voltage transient characteristic
Rated output current (rms)
Maximum peak output current (peak)
Inverter overload capacity
Bypass overload capacity
Environment
Operating temperature
Switches
Automatic retransfer switch
Interface
IBM AS/400
(normally open contacts)
RS232C ASCII interface
Options
Novell
SNMP Network Adapter
(*) Input/output figures rated for 240 volts. Output capacity will be reduced when input voltage is below 204 volts.
(**) Battery backup time may vary depending on the operating conditions and ambient temperature at the installation site.
(***) An initial charge time of 24 hrs. is necessary to obtain proper battery performance level before unit is placed in operation.
(****) At 6000 ft (2000 m) above sea level, output capacity should be derated by 3%.
Novell
is a registered trademark of Novell Inc.; IBM AS/400
TM
MODEL NUMBER UC3G2L024C6
CAPACITY
2.4 kVA (1.68 kW) (*)
Input voltage
Single phase, 208/240 Vac, +10% to -30% *
Input frequency
45 to 65 Hz
Input capacity
2.4 kVA
Input power factor
Approximate unity (0.98 to 1.0 lagging)
Less than 5% (typ)
Battery rated voltage
96 Vdc
7 mins. at full load (**)
30 mins. at half load (**)
Recharge time
Maximum 24 hrs to 100%, 90% in 10 hrs (***)
Type of batteries
Sealed lead-acid, maintenance free
Output voltage
Single-phase, 240/208/120 volts
±3%, steady state (during normal or battery-backup operation)
Output frequency
50/60 Hz ±0.1% in free-running mode (line sync range ±1.0%)
Computer-grade sine wave; less than 3.0% total harmonic distortion
with linear load
0.7 lagging
±8% under 100% load step change
125% for 1 minutes; 150% for 30 seconds
125% for 10 minutes; 1000% for 1 cycle
Crest factor
3.0
32 to 104° F (0 to 40° C)
Storage temperature
-4 to 104° F (-20 to 40° C)
Operating humidity
30 to 90%, no condensation
Altitude
Less than 3000 ft (1000 m) above sea level (****)
External dimensions
9.9W x 22.2H x 27.2D in
(250W x 564H x 690D mm)
Weight
175 lb (80.0 kg)
Acoustical noise
50 dB (A) max. output, measured 3.3 ft (1 m) from front panel
Efficiency (ac-dc-ac)
Greater than 85%
Heat generation
300W (1030 Btu/hr)
Bypass switch
Manual bypass provided
Bypass transfer switch
Static switch standard (transfer time: less than 4 mS)
Provided (this function can be disabled)
compatible signals
Signals: (1) UPS on (2) UPS battery low (3) UPS bypass active
TM
(4) utility failure
Provided
local area network
Contact Toshiba for details on these options
TM
TM
5 - 1
UC3G2L036C6
3.6 kVA (2.52 kW) (*)
3.6 kVA
144 Vdc
10.0A
15.0A
30.0A
45.0A
9.9W x 22.2H x 27.2D in
(250W x 564H x 690D mm)
220 lb (100.0 kg)
450W (1550 Btu/hr)
is a registered trademark of International Business Machines, Inc.
UC3G2L060C6
6 kVA (4.2 kW) (*)
6 kVA
216 Vdc
25.0A
75.0A
9.9W x 28.0H x 31.6D in
(250W x 700H x 790D mm)
321 lb (146.0 kg)
750W (2580 Btu/hr)

Hide quick links: