Toshiba 1400XL Plus Series Operation Manual page 8

Uninterruptible power system single phase - 2.4/3.6/6.0/8.0 kva plus
Table of Contents

Advertisement

WARNING
WARNING
DANGER
1) Verify that the UPS is off and that the power cord is disconnected from the power source.
2) Remove watches, rings or other metal objects.
3) Use tools with insulated handles to prevent inadvertent shorts.
4) Wear rubber gloves and boots.
5) Do not lay tools or metal parts on top of batteries.
6) Determine if the battery is inadvertently grounded. If inadvertently grounded, remove
source of ground.
elecrtical shock.
removed during installation and maintenance.
7) Verify circuit polarities prior to making connections.
8) Disconnect charging source and load proir to connecting or diconnecting terminals.
9) VRLA batteries contain an explosive mixture of hydrogen gas. Do not smoke, cause a flame
or spark in the immediate area of the batteries. This includes static electricity from the body.
10) Do not attempt to open the batteries in order to add water or sample the specific gravity of the
electrolyte. The batteries are valve requlated lead acid type and such servicing is not
possible without damaging the battery.
11) Use proper lifting means when moving batteries and wear all appropriate safety clothing and
equipment.
12) Do not dispose of lead acid batteries except through channels in accordance with local, state
and federal regulations.
INSTRUCTIONS IMPORTANTES CONCERNANT LA SÉCURITÉ
CONSERVER CES INSTRUCTIONS
ATTENTION
ATTENTION
Model Capacity
ATTENTION
A battery can present a risk of electrical shock and high short
circuit current.
Contact with any of a grounded battery can result in
The likelihood of such shock will be reduced if such grounds are
Manufacturer
vii
Type