Toshiba 1400XL Plus Series Operation Manual page 21

Uninterruptible power system single phase - 2.4/3.6/6.0/8.0 kva plus
Table of Contents

Advertisement

TOSHIBA
5.0
Specifications
5.1
XL Plus Series Specifications (cont'd)
MODEL NUMBER
Input
Input power factor
Input harmonic distortion
Battery
Battery rated voltage
Battery backup time when fully charged
with 0.7 power factor and 77° F (25° C)
Output
Output voltage regulation
Output voltage waveform Computer-grade sine wave; less than 3.0% total harmonic distortion
Rated load power factor 0.7 lagging
Voltage transient characteristic ±8% under 100% load step change
Rated output current (rms)
Maximum peak output current (peak)
Inverter overload capacity 125% for 1 minute; 150% for 30 seconds
Bypass overload capacity 125% for 10 minutes; 1000% for 1 cycle
Environment
Operating temperature 32 to 104° F (0 to 40° C)
Storage temperature -4 to 104° F (-20 to 40° C)
Operating humidity 30 to 90%, no condensation
External dimensions
Efficiency (ac-dc-ac) Greater than 85%
Switches
Automatic retransfer switch Provided (this function can be disabled)
Interface
IBM AS/400 TM compatible signals Signals: (1) UPS on (2) UPS battery low (3) UPS bypass active
(normally open contacts) (4) utility failure
RS232C ASCII interface Provided
Options
Novell TM local area network Contact Toshiba for details on these options
SNMP Network Adapter
(*) Input/output figures rated for 240 volts. Output capacity will be reduced when input voltage is below 204 volts.
(**) Battery backup time may vary depending on the operating conditions and ambient temperature at the installation site.
(***) An initial charge time of 24 hrs. is necessary to obtain proper battery performance level before unit is placed in operation.
(****) At 6000 ft (2000 m) above sea level, output capacity should be derated by 3%.
Novell
is a registered trademark of Novell Inc.; IBM AS/400
TM
UC3E1E024C5
(*) CAPACITY
2.4 kVA (1.68 kW)
Input voltage
Single phase, 230 Vac, +10% to -30% *
Input frequency
45 to 65 Hz
Input capacity
2.4 kVA
Approximate unity (0.98 to 1.0 lagging)
Less than 5% (typ)
96 Vdc
7 mins. at full load / 9 min. at full load (8kVA only) (**)
30 mins. at half load / 32 min. at half load (8kVA only) (**)
Recharge time
Maximum 24 hrs to 100%, 90% in 10 hrs (***)
Type of batteries Sealed lead-acid, maintenance free
Output voltage Single-phase 230 V
±3%, steady state (during normal or battery-backup operation)
Output frequency 50/60 Hz ±0.1% in free-running mode (line sync range ±1.0Hz)
with linear load
11.0A
33.0A
Crest factor
3.0
Altitude Less than 3000 ft (1000 m) above sea level (****)
9.9W x 22.2H x 27.2D
(mm)
(250W x 564H x 690D) (250W x 564H x 690D) (250W x 700H x 790D) (250W x 700H x 890D)
Weight
175 lb (80.0 kg)
Acoustical noise 50 dB (A) max. output, measured 3.3 ft (1 m) from front panel
Heat generation
300W (1030 Btu/hr)
Bypass switch Manual bypass provided
Bypass transfer
switchStatic switch standard (transfer time: less than 4 mS)
TM
5 - 3
UC3E1E036-51
UC3E1E060-51
3.6 kVA (2.52 kW)
6 kVA (4.2 kW)
3.6 kVA
144 Vdc
15.6A
46.8A
9.9W x 22.2H x 27.2D 9.9W x 28.0H x 31.2D
220 lb (100.0 kg)
321 lb (146.0 kg)
450W (1550 Btu/hr)
750W (2580 Btu/hr)
is a registered trademark of International Business Machines, Inc.
UC3E1E080-51
8kVA (5.6kW)
6 kVA
8 kVA
216 Vdc
252 Vdc
26.0A
34.7A
78.0A
104.3A
9.9W x 28.0H x 35.2D
447 lb (203.2 kg)
1000W (3444 Btu/hr)