4
Legend
1.
cover plate
2.
retaining strips
3.
orifice with stamped figures
4.1
Conversion of CHA
100 to 600 to another
gas category
34
Conversion to a different gas category
Exchanging orifices
2
1. Isolate the appliance from the power supply
from the
mains").
2. Shut off the gas supply.
Note
The burner may be hot.
3. Unscrew the cover plate (1) from the burner support.
4. Use a suitable tool to remove the retaining strips (2). Note that the retaining
strips have very sharp edges. Withdraw the retaining strips straight upwards.
Comment
The radiation shield / condensation tray can be temporarily loosened to
simplify disassembly of the burner.
5. Remove the burners one by one from their brackets at the front. To do this,
you first move them away from you and then downwards. The orifices will
now be accessible
6. Remove the orifices.
is
1
(10.3 "Isolating the appliance
Instruction manual CHA
3