Lochinvar CHA 100 G CE Installation, Commissioning, User & Maintenance Instructions page 35

Direct gas fired floor standing water heater with automatic pilot ignition
Table of Contents

Advertisement

is
Legend
Unused numbers are not applicable
1.
burner pressure regulator
4.
gas control connector
5.
blank plate
6.
supply pressure test nipple
7.
gas control
Instruction manual CHA
7. Select and fit the correct orifices from the conversion kit, based on the gas
data table
(3.4.3 "Gas
data"). The orifice diameter is stamped on the orifice
itself, see (3).
8. Re-fit the burners back in their original position.
9. Re-fit the retaining strips.
10. If the radiation shield / condensation tray was loosened, re-fasten it.
Conversion of gas control
6
7
11. Check whether there is a burner pressure regulator (1) attached to the gas
control, or simply a blank plate (5).
Comment
If the supply pressure for a gas category is the same as the burner pressure
(see the gas data table
(3.4.3 "Gas
with a blank plate with cork gasket. A burner pressure that deviates in
comparison to the supply pressure requires the use of a burner pressure
regulator with rubber gasket. Each conversion kit contains all the necessary
components.
12. If the blank plate or burner pressure regulator need to be replaced:
-
Unscrew the connector (4) of the gas control.
-
If necessary, remove the blank plate or burner pressure regulator (5)
or burner pressure regulator (1).
-
If necessary, fit the blank plate or burner pressure regulator supplied
with the conversion kit.
-
Fit the connector (4) of the gas control.
4
1
data")) then the gas control must be fitted
5
IMD-0131 R1
35