Parameter Setting Via Local Hmi; Parameter List - Siemens RDB160BN Basic Documentation

Room thermostat with bacnet ms/tp communication
Table of Contents

Advertisement

8.3.1 Parameter setting via local HMI

8.3.2 Parameter list

A6V11917618_en--_b
Access parameter settings
Press Up/Down buttons simultaneously for 5 seconds until 'Service' is
displayed on the screen.
Release and press Up button twice. Parameter P01 is displayed.
Define parameters
You can navigate through the parameter list using the Up/Down buttons.
● To change a parameter setting, select the right parameter with Up/Down
buttons and confirm by pressing the On/Off button.
● Press the Up/Down buttons to change the setting value.
● Press the On/Off button to save and go back to the parameter list.
To exit the parameter setting, either
● Go to EXIT parameter and press the On/Off button.
● Press the Up/Down buttons simultaneously.
Lock settings access
It is possible the lock the setting access via the BACnet object 'LockSettings'.
Users cannot access the parameters via the local HMI while the settings are
locked.
Name
P01
Application
P02
Control sequence
P03
Operating mode when
activating digital input 1 DI1
P04
Mold protection
P05
Dead zone Comfort mode
Communication
Control parameters
Factory setting
Range
3 = 4-pipe system 2 = 2-pipe system
3 = 4-pipe system
4 = 2-pipe system
with electric
heater
2 = Automatic
0 = Heating
change-over
control
1 = Cooling
control
2 = Automatic
change-over
based on analog
temperature
sensor or digital
input
0 = Economy
0 = Economy
mode
mode (presence)
1 = OFF mode
(windows)
0 = Not active
0 = Not active
1 = Active (the fan
never stops, even
when in controller
OFF mode)
2 K
0...10 K
8
33 | 52