Toshiba RAS-B10GKVP-E Service Manual page 42

Split type heat pump type/cooling onlytype
Hide thumbs Also See for RAS-B10GKVP-E:
Table of Contents

Advertisement

Item
Heating operation
3. Outdoor fan
motor control
1) Operation is performed at the MAX revolutions shown in the left tables for 3 minutes after com-
(Continued)
pressor operation starts and for 1 minute after defrosting operation ends.
2) Following 1) above, operation is performed at the outdoor unit fan revolutions shown in the left
tables according to the outdoor heatexchanger sensor (TE sensor) temperature.
TE
24°C
21°C
18°C
15°C
RAS-M18GAV-E
Normal operation
Econo operation
To is abnormal
RAS-M14GAV-E
Normal operation
Econo operation
To is abnormal
Operation flow and applicable data, etc.
Zone A:
Zone A: The fan revolutions are decreased by 100 rpm every 20 seconds
(to the MIN revolutions).
When Zone A operation continues for 5 minutes, the compressor
is stopped and then restarted.
Zone B:
Zone B: The fan revolutions are decreased by 100 rpm every 20 seconds
(to the MIN revolutions).
Zone C:
Zone C: The fan revolutions are decreased by 50 rpm every 20 seconds
(to the MIN revolutions).
Zone D:
Zone D: The fan revolutions are maintained at the current revolutions.
Zone E:
Zone E: The fan revolutions are increased by 50 rpm every 20 seconds
(to the MAX revolutions).
Compressor revolution (rps)
Fan revolution
To > 10°C
5.5 < To ≤ 10
–5 < To ≤ 5.5
To ≤ –5
To > 10°C
5.5 < To ≤ 10
–5 < To ≤ 5.5
To ≤ –5
Compressor revolution (rps)
Fan revolution
To > 10°C
5.5 < To ≤ 10
–5 < To ≤ 5.5
To ≤ –5
To > 10°C
5.5 < To ≤ 10
–5 < To ≤ 5.5
To ≤ –5
~20
MIN
MAX
250
400
250
400
250
600
250
600
250
400
250
400
250
600
250
600
250
400
~20
MIN
MAX
250
400
250
400
250
600
250
600
250
400
250
400
250
600
250
600
250
400
– 42 –
Description
~48
48~
MIN
MAX
MIN
MAX
250
600
250
700
250
700
250
750
250
750
250
800
250
750
250
800
250
500
250
600
250
600
250
700
250
700
250
700
250
700
250
700
250
700
250
750
To: Outdoor sensor temp. (°C)
~60
60~
MIN
MAX
MIN
MAX
250
600
250
700
250
700
250
750
250
750
250
800
250
750
250
800
250
500
250
600
250
600
250
700
250
700
250
700
250
700
250
700
250
700
250
750
To: Outdoor sensor temp. (°C)