Toshiba RAS-B10GKVP-E Service Manual page 29

Split type heat pump type/cooling onlytype
Hide thumbs Also See for RAS-B10GKVP-E:
Table of Contents

Advertisement

RAS-M10GKCVP-E, RAS-M13GKCVP-E, RAS-M16GKCVP-E
RAS-M18GACV-E
P
Pressure measurement
Gauge attaching port
Vacuum pump connecting port
Deoxidized copper pipe
Both A and B rooms
Outer dia. : 9.52mm (10,13)
:12.7mm (16)
Thickness : 0.8mm
TGb
4-way valve
(STF-0108Z)
TS
Temp. measurement
NOTE :
• The maximum pipe length of this air conditioner is 30 m. When the pipe length exceeds 20 m, the additional
charging of refrigerant, 20 g per 1m for the part of pipe exceeded 20 m is required. (Max. 200g)
*1
INDOOR UNIT
Tca
To B room
Indoor fan
Deoxidized copper pipe
Both A and B room
Outer dia. : 6.35mm
Thickness : 0.8mm
Sectional shape
of heat insulator
TGa
Muffler
Compressor
DA111A1F-20F1
Outdoor heat
exchanger
T2
Propeller fan
OUTDOOR UNIT
T1
Temp. measurement
Indoor heat
To B room
exchanger
Ta
TD
TE
TO
– 29 –
Per 1 unit
Max. : 20m
Min. : 2m
Total : 30m
Chargeless =20m
Charge
(21 to 30m)
Split capillary
Ø2.2 x 200
Strainer
Pulse motor
valve at liquid side
(CAM-B22YGTF-3)
Split capillary
Ø2.2 x 200
Refrigerant amount : 1.20kg
NOTE :
Gas leak check position
Refrigerant flow (Cooling)
=20g/m