Danfoss DHP-H User Manual page 28

Table of Contents

Advertisement

3 .2 .7
sub-menu DeFrOsT, DHP-A
This menu is specific to DHP-A.
In the "DEFROST" menu it is possible to view miscel-
laneous information about the defrost and also pos-
sible to make adjustments.
Menu text
DEFROSTS
BETW. 2 DEFR
TIME SINCE
DEFROST
FAN H OFF AT
DEFROST CURVE
MANUEL DEFR
Danfoss – 28
Description
Total number of defrosts carried out since
installation, that is, the number not reset.
The operating time of the compressor in
minutes between the 2 last defrosts.
The operating time of the compressor in
minutes since last defrost. Reset after a
defrost is completed.
Fan high speed is deactivated at this
outdoor temperature and low speed is
activated.
Here, the angle of the defrost curve can
be changed using the right-hand arrow
and by either pressing + or -. (Change the
start temperature for when defrosting is
to begin).
By using the right-hand arrow and then
pressing +, defrost can be started manu-
ally (shunts +20°C for 10 minutes).
VUBMA102
DEFROST
DEFROSTS
BETW. 2 DEFR
TIME SINCE DEFROST
FAN H OFF AT
DEFROST CURVE
MANUEL DEFR
Adjusted by:
Not adjustable
Not adjustable
Not adjustable
By the customer,
if necessary.
By the customer,
if necessary.
By the customer,
if necessary.
0 S
0 M
0 M
12°c
0