2
1
fi g. 19

Connecting external controls

LT.AL.W7H.000.024
Remeha Avanta Plus
Manufacturer
Supply voltage
Pre-purge time
Post-purge time
Ignition time
Safety time
Anti-cycling time
Fuse value F1 (230 V)
DC fan
table 04
Control unit characteristics
Any loads other than those specified above are only allowed if
an isolating transformer is used.
The output of the Remeha Avanta Plus can be controlled in
the following ways: Options
1. On/off control – volt free switching - The boilers internal
control will modulate the output to achieve the flow tem-
perature set point of the boiler. This contact is on the con-
nectors 7 and 8 on terminal block X9 (low voltage only).
2. Modulated control – Open Therm - The external controls
will modulate the boiler's output to achieve the flow temper-
ature determined by the modulating regulator. This contact
is on the connectors 7 and 8 on terminal block X9 (low volt-
age only).
3. On/off control – 230 V switching - The boilers internal
control will modulate the output to achieve the flow tempera-
ture set point of the boiler. This contact is on the connector
1 on terminal block X2 (230 VAC only).
4. Modulated control – Open Therm in combination with an
externally mounted simple 230 V switching time clock -
The boiler will provide room compensated heating and time
control over CH and DHW (System boiler), use options 1 & 2.
• All connections on terminal X1, X2, X4, X5, X6 and X7
are 230 VAC.
• All connections on terminal X9 are low voltage only.
2.7
Connecting external controls
• Release the two screws at the bottom of the front casing
and remove the front casing.
• Feed the cables through the grommet in the base of the
boiler.
• Connect the cables to the relevant connectors, as shown in
the diagrams.
• Isolate power supply at the fused spur before carrying out
any work on the boiler controls.
20
Sit Controls
230 V – 1ph – 50 Hz
3 s
5 s
2.5 s
5 s
3 till 10 min.
2 AT
24 VDC