Remeha Avanta Plus
Please ensure that the new boiler plant is not in circuit when
the flushing takes place, especially if cleansing chemicals are
used to assist the process.
It is important to check the inhibitor concentration after installa-
tion, system modifications, filling the system and every service
in accordance with these instructions.
For the correct dosage and the suitability of inhibitors for use
with our boilers and for further information on water treatment
or system cleaning we advise direct contact with either of the
following companies:
®
'F1
' manufactured by:
Fernox, Cookson Electronics
Forsyth Road
Sheerwater
Woking
Surrey GU21 5RZ
Tel No: 01483 793200
Fax No: 01483 793201
Email: admin@fernox.com
Web site: www.fernox.com
or:
®
Sentinal 'X100
' manufactured by
Sentinel Performance Solutions
The Heath Business & Technical Park
Runcorn
Cheshire,
WA7 4QX
Tel No: 0800 389 4670
Fax No: 0800 389 4677
Email: info.uk@sentinel-solutions.net
Web site: www.sentinel-solutions.net
2.3.5

Safety valve discharge

A pressure relief safety valve is fitted in the boiler set to the
maximum operating pressure of the boiler of 3 bar.
If the pressure in the boiler becomes too high the pressure
is relieved by releasing water to outside via the safety valve
discharge pipe. The discharge pipe should be fitted in accord-
ance with British Standards and must be at least 15 mm Ø.
The pipe should be positioned so that the discharge of water
or steam is visible and cannot create a hazard to the occu-
pants of the premises or damage the electric components and
wiring. In addition the discharge should be located where it is
unlikely to cause damage to the premises.