PELLET VENT TERMINATION:
•
Termination must be a minimum of 12" above
the chase cap (DIM "A) (note: the chimney must
meet local codes for height above the roof or
other obstructions)
•
Must have an approved cap (B) (to prevent wa‐
ter from entering) or a 45* elbow downturn.
•
If the termination is located on the predomi‐
nantly windy side of the house, an approved
house shield is recommended to prevent soot
from accumulating on the side of the house.
•
Must not be located where snow or other mate‐
rials such as leafs, snow or grass, could block it.
•
Must have a "Metal Seal Plate" or "Wall Thim‐
ble" at point (C)
•
Horizontal terminations must protrude 12" from
the wall, vertical terminations 24"
•
Minimum 3' clearance above any forced air in‐
take of any other appliance within 6'.
•
Minimum 3' above a gas meter/regulator within
3' horizontally of the vertical centre line of regulator.
•
Minimum 6' clearance to a gas service regulator vent out‐
let.
•
Minimum 1' clearance under veranda, porch, deck or bal‐
cony. Permitted only if structure is fully open on a mini‐
mum of two sides beneath the floor.
VS0952_E
E
S
XHAUST
YSTEM
12/30/2009
(C
)
ONTINUED
12