Ref. #
Reporting Code
[00040316] Closing Delinquency
[00040316] Walk Test Enabled
[00040316] Walk Test Disabled
[00040316] General System Trouble/Rest.
[00040316] General Device Low Battery/
Rest.
[00040316] Gen Module Comm Fault/
Rest.
50
Code Sent When...
programmed number of days for delinquency
has expired without partition being armed
walk test mode entered
walk test complete
indicates one or more of following:
PC4204/PC4204CX/PC4820/PC4702/PC4850***/
Alternate Communicator*** AC, battery and
Aux Supply troubles/rest., PC440X troubles,
automation fault, PC4164 RF jam
NOTE: When the system is being used in a fire
applications, a General System trouble should
be considered as a Fire trouble.
Wireless zones/pendants (WLS908) 009-128;
handheld keypads (WLS910)
wireless keys (WLS909)
control panel loses communications with con-
nected module(s)
** PPP = partition number; UUU = user number (user 1000 to 1500 = 999); ZZZ = zone number
*** Not UL Listed. Do not use in conjunction with UL Listed systems
Dialer
Contact
Direction*
O
O
O
O
O
O
* A/R = alarms/restorals; O/C = openings/closings; O = other
SIA Auto Rep
ID
Codes**
(4) 54
CD-000
(6) A7
TS-000
(6) A7
TE-000
(3) 3A
YX-000/YZ-000
(3) 84
XT/XR-ZZZ
XT/XR-901-904
XT/XR-921-936
(3) 33
ET-000/ER-000