5. FIELD DEVICE TERMINATION

5.1 TERMINATING THE DETECTION AND ALARM (SOUNDER) CIRCUITS

All cables entering the enclosure should use cable glands. The Detector and Sounder circuits should be connected to the
appropriate connector block on the Termination PCB as shown in Figure 6 below. All screens should be fed through the gland to
make electrical contact with it, and be terminated at the brass earthing strip as shown below (see Figure 6)
(For detailed detector and alarm circuit wiring diagrams, please refer to pages 6 and 7.)

5.2 AUXILIARY OUTPUT TERMINATIONS

Connect auxiliary output cables to the appropriate connector block terminals on the Termination PCB (See Page 15). Screened
cables should be terminated as per figure 6.
For a full description of the inputs and outputs available on the Infinity range of Fire Panels, including typical wiring diagrams please
refer to pages 6 & 7.