13. ENGINEER OPTIONS (8 WAY CONFIG DIP SWITCH)

The Infinity FCP has the following configuration options:
Switch 1 ON = Compatibility Mode – use if Fyreye II Detectors are NOT used
Switch 2 ON = Zone 2 non latching
Switch 3 ON = Sounder circuit 3 active giving a power output
Switch 4 ON = Sounder circuit 4 active giving a power output
Switch 5 ON = DUTCH MARKET ONLY
Switch 6 ON = Fault relay activates on a fire condition (Giving 2 fire relays)
Switch 8 ON = Makes the last zone on the panel a call point zone (alarms from that zone not delayed)
Note: The above options my not comply with local regulations. Please check with the relevant codes of practice in your region.
Approved Document No. GLT-201-7-1
Issue: 1.6
Author: NRPJ
0086
Zeta Alarm Systems by GLT Exports Ltd,
72-78 Morfa Road, Swansea SA1 2EN
0086-CPD-575041
EN54-2:1997+A1:2002 + A2: 2006
EN54-4:1997+A1:2002 + A2: 2006
Control and indicating equipment for fire detection and fire
alarm systems for buildings
Infinity Conventional Fire Panel
IN1, IN2, IN4, IN6, IN8
Provided options:
Output to fire alarm devices
Delays to outputs
Test Condition
Other Technical Data: See Doc: "Infinity 8 Product file"
held by the manufacturer
Date: 27/7/2012