Liebert Static Transfer Switch 2 Installation, Operation & Maintenance Manual page 87

100-1000 amp, 50-60 hz
Hide thumbs Also See for Static Transfer Switch 2:
Table of Contents

Advertisement

The value parameter settings are in the form of a bit-packed word (in hexidecimal notation). In
other words, each bit indicates a particular setting for the option or feature. The bit assignments
for the options and features are as follows:
Options_1
bit0 —HasDualOutputBreaker
bit1 — HasPDU
bit2 — Has4PoleTransferSwitch
bit3 — HasShuntTrip
bit4 — HasWyeOutputXfmr
bit5 — HasExternalPrecisionTimeSource
bit6 — HasSFA
bit7 — HasRemoteSourceSelect
bit8 through bit15 — not used (set to 0)
Comms Options 1
bit0 — HasIntModem
bit1 — HasExtModem
bit2 — HasNIC
bit3 — not used (set to 0)
bit4 — HasSiteScan
bit5 — not used (set to 0)
bit6 — not used (set to 0)
bit7 — HasOpenCommsDigitalInputBrd
bit8 — HasOpenCommsDigitalOutputBrd_1
bit9 — HasOpenCommsDigitalOutputBrd_2
bit10 — HasRemoteStatusPanelBrd_1
bit11 — not used (set to 0)
bit12 — not used (set to 0)
bit13 — not used (set to 0)
bit14 — EnableDialIn
bit15 — EnableDialOut
Comms Options 2
bit0 — EnablePager
bit1 — EnableOCDINormallyClosed
bit2-3 — OCDO1Assignment (0=User Defined, 1=Standard Set or 2=AS400)
bit4-5 — OCDO2Assignment (0=User Defined, 1=Standard Set or 2=AS400)
bit6 through bit15 — not used (set to 0)
Critical Option Enabling
bit0—EnableManual_IPeakReset
bit1—EnableAutoRestart
bit2 through bit15 - not used (set to 0)
Non-Critical Option Enab
bit0 — EnableAutoReXfer
bit1 through bit15 — not used (set to 0)
Communication Interfaces
75