Figure 44 Modem Dialog Box - Liebert Static Transfer Switch 2 Installation, Operation & Maintenance Manual

100-1000 amp, 50-60 hz
Hide thumbs Also See for Static Transfer Switch 2:
Table of Contents

Advertisement

Figure 44 Modem Dialog Box

2. Select the type of modem that the STS2 will be using:
• Select INT if the STS2 will be communicating via an internal modem.
• Select EXT if the STS2 will be communicating via an external modem.
3. Select the PRIMARY LINE choice to enter the primary telephone number for the modem to
dial when an alarm is triggered.
4. Enter the number in the keypad dialog box.
5. Select OK to save the telephone number. The number is displayed in the field adjacent to the
Primary Line choice.
6. Select the SECONDARY LINE choice to enter the secondary telephone number for the modem
to dial when an alarm is triggered.
7. Enter the number in the keypad dialog box.
8. Select OK to save the telephone number. The number is displayed in the field adjacent to the
Secondary Line choice.
9. Select INIT. STRING to configure the initialization string.
This string configures the parameters of the modem.
• This setting only needs to be configured if an external modem is used. Check your modem's
documentation for this setting.
• The string for the internal modem set by the manufacturer and does not need to be
changed.
10. Select BAUD RATE to display a dialog with the baud rate choices:
• For an external modem, select from 2400 bps, 9600 bps or 19200 bps.
• An internal modem only supports 2400 bps.
STS2 Touch Screen Display
89