Emergency Transfer; Load Current Transfer Inhibit; Scr Failure; On/Off Sequence - Liebert Static Transfer Switch 2 Installation, Operation & Maintenance Manual

100-1000 amp, 50-60 hz
Hide thumbs Also See for Static Transfer Switch 2:
Table of Contents

Advertisement

9.1.4

Emergency Transfer

To ensure that power remains connected to the load, the STS2 automatically performs an emer-
gency transfer from one input source to the other when an outage occurs on the existing source.
The automatic transfer takes place if the other source's voltage is within acceptable limits, and
regardless of the phase difference between the two sources.
Emergency transfers occur with a loss of power on the output of less than 4 ms.
Emergency transfers from the alternate source to the preferred source are not affected by the Auto
Retransfer Enabled/Disabled or Retransfer Delay user settings.
9.1.5

Load Current Transfer Inhibit

The STS2 senses the load current. If the load current exceeds the preset level deemed to represent
a load inrush or fault condition, the unit's logic disables manual and automatic transfers, even if
the selected source's input voltage is outside the acceptable limits. This event triggers an I-Peak
alarm. If so configured, the Load Current Transfer Inhibit is automatically reset after the current
and voltage return to within normal parameters. This reset provides continued protection against a
source failure. The Load Current Transfer Inhibit also can be programmed to require a manual
reset. See step14. on page 86 under the Source Set Points heading for details.
9.1.6

SCR Failure

The STS2 continuously monitors the status of the SCR switching devices for proper operation. In
the event of a shorted SCR on the input source powering the load, the STS2 automatically triggers
an alarm and trips open the other source isolation breaker. In the event of a shorted SCR on the
other input source, the STS2 automatically triggers an alarm and trips open the other source isola-
tion breaker.
In the event of an open SCR, the switch automatically triggers an alarm and transfers the load to
the other source. All open and shorted SCR alarm conditions are latched and require the system to
be repaired and reset to restore normal operation.
9.1.7

On/Off Sequence

The STS2 contains no master On/Off push button control. When connected to the input sources,
the unit's logic power comes on automatically. The touch screen display (if so equipped) is active as
long as at least one input source is energized and the Control Power Disconnect (located inside the
static switch) is on.
9.2

Detailed Component Description

9.2.1

Controls

Operator Interface
The STS2 Color Graphical Display unit contains a touch screen color LCD to provide the operator
interface to control and configure the operation of the unit and quickly diagnose problems. A pass-
word and an optional keylock, if installed, are provided for security.
The LED Display unit includes push-buttons for source transfer, alarm reset and audible alarm
silence.
Theory of Operation
55

Advertisement

Table of Contents
loading

Table of Contents