11. Configure the MODEM HEALTH CHECK.
The Health Check verifies that the modem is working properly. This setting allows you to
enable the check and set when it is run.
a. Select the button to display the Modem Health Check dialog box, from which you can access
further dialogs to set the time and days that the check is run.
b. Select SAVE to keep the settings.
The Health Check dialog box is closed and the Modem dialog box is again active.
c.
Select YES in the Modem dialog box to activate the Modem Health Check.
If you select NO, the Modem Health Check is not run.
12. Configure AUTO DIAL IN.
Auto Dial In allows a user to dial into the STS2 through the modem to check status and access
the system via a hyperterminal connection.
a. Select YES to activate the dial in feature.
b. Select NO to deactivate the dial in feature.
13. Configure AUTO DIAL OUT.
Auto Dial Out allows the STS2 to automatically dial out to a system to notify a user of an event
or status.
a. Select YES to activate the dial out feature.
b. Select NO to deactivate the dial out feature.
14. Select SAVE to keep the modem configuration settings.
15. Select YES in the Comm Options dialog box to activate the settings.
You are returned to the Comm Options dialog box.
Configuring Pager Support
Pager support will be implemented in an upcoming update of the system. This support will trigger
the system to call a pager when specified events occur. This menu choice will allow you to enter the
telephone number and PIN for the pager that you want the system to call.
Configuring the Input Contact Isolator Settings
The Input Contact Isolator (ICI) is an optional, eight-channel input board for up to eight external
user alarm or message inputs to be routed to the static transfer switch's alarm network.
The contact is set to either be normally open or normally closed. When a contact closes or opens, an
event is triggered. See 6.2 - Input Contact Isolator Board on page 19 for more information on
the ICI.
The Input Contact Isolator options are configured through the Input Contact Isolator dialog box,
which is accessed from the Comm Options dialog box. The Input Contact Isolator dialog box con-
tains eight choices to match the eight channel input board. You can label each button to identify the
event associated with the contact. When the dialog box is accessed, each button flashes to display
the Input Contact Isolator number and the user entered label. This label also appears in the Dis-
play Panel when an event related to an Input Isolator Connector is triggered.
The Input Contact Isolator dialog box allows you to:
• Label the input contact assignments for your setup.
• Set the delay for an external event triggering an alarm.
• Review the isolator contact assignments, once the labels are entered.
The delay allows you to set the number of seconds which a condition needs to persist to trigger an
alarm.
These input alarms can also be configured to activate a programmable relay output, which is dis-
cussed in Configuring the Programmable Relay Board Settings on page 91.
To configure the Input Contact Isolator relays:
1. Select INPUT CONTACT ISOLATOR from the Comm Options menu.
The Input Contact Isolator dialog box is displayed.
90