Logs; Figure 48 Event Log - Liebert Static Transfer Switch 2 Installation, Operation & Maintenance Manual

100-1000 amp, 50-60 hz
Hide thumbs Also See for Static Transfer Switch 2:
Table of Contents

Advertisement

System ID
Most of the settings for System ID are set by Liebert either at the factory or when the unit is
installed.
Order No., System Tag No., System ID No. and Model No. are the numbers used to identify and
track the system.
Language, Time and Date are synchronized with the location of the unit.
The only configurable field is the Password. See Using the Password on page 81 for more infor-
mation on configuring and using the password.

13.6.2 Logs

Two types of logs are kept by the STS2: Event Log and History Log.
Event Log
The Event Log tracks the alarms and faults of the STS2.
See 11.0 - Alarm and Faults on page 65 for more information on these events and see 11.2.1 -
Event Log for more information on the Event Log and definitions of the fields displayed in the
Event Log screen.

Figure 48 Event Log

To use the Event Log:
1. Select LOGS from the menu bar to open the Logs menu.
2. Select EVENT LOG from the menu.
3. Use the UP and DOWN buttons to scroll through the event list.
4. Select OK to close the Event Log. The data remains in the log.
History Log
Two History Logs are available to track major alarms. If so configured, an alarm freezes the history
buffer. When the History Status buffer is frozen, a History Log is created that can be accessed from
the HISTORY LOG x choices in the LOGS menu.
See 11.2.2 - History Log for more information on the History Logs and definitions of the fields
displayed in the History Log screen.
STS2 Touch Screen Display
95