Liebert Static Transfer Switch 2 Installation, Operation & Maintenance Manual page 145

100-1000 amp, 50-60 hz
Hide thumbs Also See for Static Transfer Switch 2:
Table of Contents

Advertisement

If configured to be a latching alarm, press RESET on the display. If you are accessing the unit from a terminal, type
CA and press RETURN on your keyboard.
HIST LOGS FULL
History Logs Full
The history buffer has reached its capacity for both history logs. No further history logs can be written until the logs are
cleared. The History Logs were frozen by the occurrence of two designated faults or alarms.
Both history logs have been frozen by significant events. These logs contain valuable diagnostic data regarding those
events which may be useful if service is required. Once the logs have been analyzed and the causes for freezing them
have been resolved, the history logs should be cleared to make them available for capturing future events.
To clear the History Logs, select the CLEAR HLOG button under the LOGS > HISTORY LOG 1 or LOGS > HISTORY
LOG 2 menus to clear the History Status buffer after the alarms have been resolved.
If you are accessing the unit from a terminal, type CHL and press RETURN to clear the History Logs.
Press SILENCE on the touch screen to turn off the audible alarm, if so configured. If you are accessing the STS2
system from a terminal, type SH and press RETURN on your keyboard to turn off the audible alarm.
The event was written to the Event Log, if so configured.
The alarm has triggered a message to be sent to the modem, if so configured.
If configured to be a latching alarm, press RESET on the display. If you are accessing the unit from a terminal, type
CA and press RETURN on your keyboard.
Event Message Help Text
133