Figure 46 Programmable Relay Board Dialog Box; Table 15 Standard Settings For Programmable Relays - Liebert Static Transfer Switch 2 Installation, Operation & Maintenance Manual

100-1000 amp, 50-60 hz
Hide thumbs Also See for Static Transfer Switch 2:
Table of Contents

Advertisement

The STANDARD SET for the Programmable Relay Board settings are:
Table 15
Standard Settings for Programmable Relays
Relay
1
SOURCE 1 FAIL
2
SOURCE 2 FAIL
3
BYPASS CB4 CLOSED
4
BYPASS CB5 CLOSED
5
TRANSFER INHIBIT
6
OUT OF SYNC
7
EQUIP OVER TEMP
8
blank
The USER DEFINED SET allows you to assign faults and alarms to each contact on the relay
boards.
Utilizing the USER DEFINED SET, you can also select Input Contact Isolators to associate with a
programmable relay.
In addition individual events, three other assignment choices are available:
• SELECT ALL sends a summary event to the selected relay whenever any event occurs. If this
setting is selected for a relay, no other event needs to be assigned for that relay.
• ON SOURCE 1 or ON SOURCE 2 can be assigned to a relay to send a notification when that
source is being used by the load.
Once configured, the static transfer switch continuously checks the status of the items defined for
each contact and updates the state of the relay.
To configure your programmable relay boards for user defined settings:
1. Select PROG. RELAY BOARD # x from the Comm Options dialog box, where x is the
corresponding board number.
The Prog. Relay Board dialog box is displayed.

Figure 46 Programmable Relay Board Dialog Box

92
STS2 Touch Screen Display
Setting
Source 1 failure.
Source 2 failure.
Switch (CB4) is closed, Source 1 is bypassed.
Switch (CB 5) is closed, Source 2 is bypassed.
A transfer between Source 1 and Source 2 is being restrained.
The phase difference between sources 1 and 2 exceeds the
allowable threshold for transfer,
The ambient temperature of the STS2 exceeds the
recommended threshold for operation.
No setting.
Definition