Table 9
Event Messages
ID
Alarm Message
001
S1 SCR SHORT
002
S2 SCR SHORT
003
S1 SCR OPEN
004
S2 SCR OPEN
005
PRIMARY FAN FAIL
006
CONTROL MODULE FAIL
007
PWR SPLY DC A FAIL
008
PWR SPLY DC B FAIL
009
PWR SPLY S1 AC FAIL
010
PWR SPLY S2 AC FAIL
011
PWR SPLY LOGIC FAIL
012
OUT VOLT SENSE FAIL
013
S1 VOLT SENSE FAIL
014
S2 VOLT SENSE FAIL
015
S1 SCR SENSE FAIL
016
S2 SCR SENSE FAIL
017
S1 CURR SENSE FAIL
018
S2 CURR SENSE FAIL
019
S1 GATE DRIVE FAIL
020
S2 GATE DRIVE FAIL
021
INTERNAL COMM FAIL
022
EXTERNAL COMM FAIL
023
CB1 SHUNT TRIP FAIL
024
CB2 SHUNT TRIP FAIL
064
HEATSINK OVERTEMP
067
S1 UV
068
S1 UV (RMS)
069
S1 OV
070
S1 OF/UF
071
S1 FAIL
072
S2 UV
073
S2 UV (RMS)
074
S2 OV
075
S2 OF/UF
076
S2 FAIL
077
S1 OVERCURRENT
078
S2 OVERCURRENT
079
S1 I-PEAK
080
S2 I-PEAK
081
SOURCES OUT OF SYNC
082
LOAD ON ALT SOURCE
68
Alarm and Faults
Description/Cause
One or more of the SCRs for Source 1 have shorted and
failed.
One or more of the SCRs for Source 2 have shorted and
failed.
One or more of the SCRs for Source 1 is open.
One or more of the SCRs for Source 2 is open.
A primary cooling fan has failed and the unit is now being
cooled by a secondary fan, which is not monitored.
Control logic module has failed.
Power supply DC bus A has failed.
Power supply DC bus B has failed.
Power supply Source 1 AC has failed.
Power supply Source 2 AC has failed.
A power supply module has failed.
The output volt sense module failed
The Source 1 volt sense module failed.
The Source 2 volt sense module failed.
The Source 1 SCR sense module failed.
The Source 2 SCR sense module failed.
The Source 1 SCR current module failed.
The Source 2 SCR current module failed.
The Source 1 gate drive module failed.
The Source 2 gate drive module failed.
Internal CAN communications failed.
Options CAN communications failed.
CB1 shunt trip failed.
CB2 shunt trip failed.
Heatsink has exceeded the recommended temperature.
Source 1 under voltage, fast detection.
Source 1 under voltage, slow detection.
Source 1 over voltage
Source 1 over frequency/under frequency
Source 1 failure.
Source 2 under voltage, fast detection.
Source 2 under voltage, slow detection.
Source 2 over voltage.
Source 2 over frequency/under frequency.
Source 2 failure.
Source 1 over current.
Source 2 over current.
I-PK on Source 1.
I-PK on Source 2.
Source 1 and Source 2 are out of synchronization.
The output load is running on the alternate source.
Action
D, F, A, E
D, F, A, E
D, F, A, E
D, F, A, E
D, A, E
D, A, E
D, A, E
D, A, E
D, A, E
D, A, E
D, A, E
D, A, E
D, A, E
D, A, E
D, A, E
D, A, E
D, A, E
D, A, E
D, A, E
D, A, E
D, A, E
A, E
A, E
D, A, E
A, E
A, E
L, A, E
A, E
A, E
A, E
A, E
A, E
A, E
A, E
A, E
A, E
A, E
A, F, E
A, F, E
A, E
A, E