15.1.4 Grounding
Refer to 5.3 - System Grounding on page 15 for specifications and instructions regarding ground-
ing.
15.1.5 Electrical Requirements
Table 20
Electrical Requirements
Item
Maximum Continuous Current
Load Power Factor Range
Load Crest Factor
Source Voltage Distortion
Overload Capability
Table 21
Unit Short Circuit Withstand Capability
Unit Voltage
208-240V
380-480V
600V
15.1.6 Input Surge Suppression
The STS2 is equipped with transient voltage surge suppression on each input for maximum surge
suppression. The surge suppression is capable of protecting the STS2 from operating outside of tol-
erances due to surges as defined by IEC 1000-4-5 (1.2/50uS surge, 2kV CM and 1kV DM) as
required under EN 50091-2.
15.1.7 Response Time
A dual level fast/slow transfer threshold is used for under voltage detection to allow the STS2 to be
compatible with UPSs and generators. The voltage thresholds and the slow transfer delay time is
user-adjustable. The fast transfer delay time is less than 4 ms.
The over voltage detection uses a single threshold, with programmable level and delay time.
See User Settings on page 83 for instructions on configuring these settings.
15.1.8 Environmental Requirements
See 3.0 - Location Considerations on page 10 for details concerning environmental require-
ments for the STS2.
108
Specifications
100, 250, 400, 600, 800, 1000 amps
0.75 to 1.0, leading or lagging
Up to 3.5
Up to 10% THD with notches and ringing transients
125% for 30 minutes 100A-400A
125% for 10 minutes 600A-1000A
150% for 2 minutes
500% for 0.25 sec.
Unit Amps
Withstand Capability
100-250A
100kA
400-600A
100kA
800-1000A
100kA
100-250A
65kA
400-600A
100kA
800-1000A
65kA
100-250A
25kA
400-600A
25kA
800-1000A
42kA
Requirement