Detailed Control Functions
2.4

Normal Operation

2.4.1 List of Functions in Normal Operation
Part Name
Compressor
Outdoor unit fan
Four way valve
Electronic expansion
valve (Main)
Electronic expansion
valve (Main 2)
Electronic expansion
valve (Subcooling)
Solenoid valve (Hot
gas)
Solenoid valve
(Receiver gas vent)
Solenoid valve (Circuit
of oil return)
Solenoid valve (Close
liquid pipe for stopped
outdoor unit)
Solenoid valve (Main
electronic expansion
valve bypass)
Solenoid valve
(Refrigerant regulator
gas vent pipe)
Solenoid valve
(Refrigerant regulator
liquid pipe)
Solenoid valve
(Refrigerant regulator
gas pipe)
Solenoid valve
(Refrigerant regulator
liquid outlet)
Solenoid valve
(Receiver liquid level)
Solenoid valve (Mixing
unit inlet)
Solenoid valve (Bypass)
Solenoid valve (Oil
regulator outlet)
Indoor unit fan
Indoor unit electronic
expansion valve
46
Electric Symbol
RQYQ8P
PQYQ10·12P
M1C
M1C
M2C
M1F
M1F
Y3S
Y3S
Y1E
Y1E
Y2E
Y2E
Y1S
Y1S
Y8S
Y8S
Y5S
Y5S
Y6S
Y6S
Y10S
Y10S
Y11S
Y11S
Y12S
Y12S
Y13S
Y13S
Y14S
Y14S
Y7S
Y7S
Y4S
Y4S
Y2S
Y2S
Y9S
Y9S
M1F
M1F
Y1E
Y1E
Normal Cooling
PQYQ14·16P
M1C
M2C
PI Control
M3C
Depends on the
M1F, M2F
mode of the cooling
heat exchanger
Y3S
OFF
Y1E
2000 pls
Y2E
Depends on the
control of the
Y3E
electronic expansion
valve
Y1S
OFF
Y8S
OFF
Y5S
ON
Y6S
OFF
ON
Y10S
OFF
Y11S
OFF
Y12S
OFF
Y13S
OFF
Y7S
OFF
Y4S
OFF
Y2S
OFF
Y9S
ON
Depends on the
M1F
indoor unit
Depends on the
Y1E
indoor unit
SiBE341027
Normal Heating
PI Control
Depends on the
mode of the cooling
heat exchanger
ON
Depends on the
control of the
electronic expansion
valve
0 pls
OFF
OFF
ON
ON
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
Depends on the
indoor unit
Depends on the
indoor unit
Function