Mitsubishi Electric ME96NSR Operator's Manual page 15

Electronic multi-measuring instrument ns series
Hide thumbs Also See for ME96NSR:
Table of Contents

Advertisement

■ Simplified Set-up Contents List
<Setting page: P-1>
Phase wire
Display pattern
00:P00 11:P11
1:3P3W (2CT)
2:3P3W (3CT)
01:P01 12:P12
02:P02 13:P13
3:3P4W
03:P03
04:P04
05:P05
06:P06
07:P07
08:P08
09:P09
10:P10
VT secondary
voltage
[3P4W]
1:63.5V
2:100V
3:110V
4:115V
5:120V
[3P3W]
1:100V
2:110V
3:220V
VT primary current
[Exponent value]
0:60 to 999V
1:1000 to 9990V
2:10000 to 99900V
3:100000 to 750000V
[Voltage value]
(100 digits) (10 digits) (1 digit)
0 to 9
0 to 9
0 to 9
■ Simplified Set-up
In the operation mode, press
SET
By pressing
in the simplified set-up mode, the simplified setting page is changed.
PHASE
+
,
Set the set-up menu number to "End".
Set-up menu
Press
or more.
PHASE
+
For 1 secend or more
DISPLAY
DISPLAY
+
,
① Phase wire
② Set the display pattern.
DISPLAY
SET
+
,
00 : P00
② Display pattern
to
13 : P13
DISPLAY SET
+
,
③ Using VT/direct input
④ Set the rated voltage scaling for the bar graph.
DISPLAY SET
If you set "1: using VT" on set up No. ③ , this content
cannot be set.
+
,
④ Direct voltage
[3P3W]
1 : 110V
2 : 220V
DISPLAY SET
+
,
⑤ VT secondary voltage
⑥ Set the primary voltage values of VT.
If you set "0: direct input" on set up No. ③ , this content
DISPLAY SET
cannot be set
It is set by the top 3 digits voltage values and the exponent
+
,
values (10 to the n-th power).
⑥ VT primary voltage
The set-up order is the exponent values and the voltage values.
Exponent values: 0 (10
DISPLAY SET
Using VT
Direct voltage
/direct input
[3P4W]
1:110V/63.5V
0:direct input
2:173V/100V
1:using VT
3:190V/110V
4:380V/220V
5:415V/240V
6:440V/254V
7:480V/277V
[3P3W]
1:110V
2:220V
CT primary current
Time constant
for current
[Exponent value]
demand
0:5.0 to 9.9A
00:0s
10:5min
1:10 to 99A
01:10s
11:6min
2:100 to 990A
02:20s
12:7min
3:1000 to 9900A
03:30s
13:8min
4:10000 to 30000A
04:40s
14:9min
05:50s
15:10min
06:1min 16:15min
[Current value]
07:2min 17:20min
(10 digits) (1 digit)
08:3min 18:25min
0 to 9
0 to 9
09:4min 19:30min
and
simultaneously for 2 seconds or more, and the following operation becomes available.
RESET
and
simultaneously for 1 second
PHASE
DISPLAY
[3P4W]
1 : 100/63.5V
5 : 415/240V
2 : 173/100V
6 : 440/254V
3 : 190/110V
7 : 480/277V
4 : 380/220V
0
= 1 time)
Voltage values: the top 3 digits (0 to 9)
1
1 (10
= 10 times)
Example: Set-up to 10000V
2
Exponent values: 2
2 (10
= 100 times)
3 (10
3
= 1000 times)
Voltage values: 100
<Setting page: P-2>
Communication
method
1:CC-Link
2:ModBus
ModBus parity
0:non
1:odd
2:EVEn
ModBus
CC-Link
stop bit
station number
01 to 64
1:1
2:2
① Set the phase wire.
1 : 3P3W 2CT
2 : 3P3W 3CT
3 : 3P4W
③ Set using VT or direct input (without VT).
0 : direct input.
1 : using VT
⑤ Set the secondary voltage values of VT.
If you set "0: direct input" on set up No. ③ , this content
cannot be set.
[3P3W]
[3P4W]
1 : 100V
1 : 63.5V
2 : 110V
2 : 100V
3 : 220V
3 : 110V
ModBus
ModBus
baud rates
address
1:2400bps
001 to 255
2:4800bps
3:9600bps
4:19.2kbps
5:38.4kbps
CC-Link
Communication
Baud rates
module reset
1:156kbps
0:OFF
2:625kbps
1:ON
3:2.5Mbps
4:5Mbps
5:10Mbps
4 : 115V
5 : 120V
13