Mitsubishi Electric ME96NSR Operator's Manual page 30

Electronic multi-measuring instrument ns series
Hide thumbs Also See for ME96NSR:
Table of Contents

Advertisement

Three-phase Automatic Power Factor Adjustment Device
This device automatically controls power condenser input and adjusts power factor.
Power loss and voltage rise can be prevented by using this device.
● Features
• Lineup of 6-Circuit and 12-Circuit Control Types
Only one device is needed where many condensers are needed in 12-circuit control such as large facility or
low-voltage control.
• Better Accuracy for Power Factor Measurement
Accuracy has improved compared to the previous model from ±5% to ±2% leading to better power factor
control.
• Automatic Condenser Capacity Awareness Function
Inherits our own condenser capacity awareness function, and set-up of the device is very easy.
New function of condenser capacity lock is added.
• Better Visibility with Large LCD Display
With the large LCD display, current power ratio plus (voltage, current, active power, reactive power) and
various setting value can be displayed.
● Dimensions
● Specifications
Model Name
Phase Line
Instrument
Rating
Alternating Current (A),
AC Voltage (V), Active Power (W),
Measuring
Reactive Power (var),
Items
Apparent Power (VA)
Power Factor (cos f)
Control Method
Control
Specifications
Relay Output
Operation Complete Signal
Input/Output
Specifications
Operation Prohibited Output
Auxiliary Power Supply
Note: VAR-6A/VAR-12A does not have CE marking.
28
144
Current
Voltage
Frequency
Automatic
Cyclic Control / Preference Control / Optimum Control
Manual
Manual ON / Automatic / Manual OFF
Output Contact
Full-time Excitation, No Voltage a Contact, 6-Circuits / 12-Circuits, One-way Common
Contact Capacity
250VAC 1.0A, 110VDC 0.1A
Input Complete Signal, Cutoff Complete Signal
No Voltage a Contact, One-way Common, Contact Capacity 24VDC 0.1A
Input Prohibited Signal, Cutoff Prohibited Signal 5VDC 15mA,
Enforced Cutoff Signal 5VDC 25mA
100 to 240VAC (+10%, -15%), 100VDC (-25%, +40%)
113
15
98
79.5
VAR-6A / VAR-12A
3-Phase/3-Wire, 3-Phase/4-Wire Common Use
5AAC
110VAC, 220VAC (3-Phase/3-Wire)
Max. 254/440VAC (3-Phase/4-Wire)
50-60Hz Common Use
Degree 1.0
Degree 2.0
VAR-6A
Unit : mm
Conforms to JIS C 1102

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Me96nsr-mb

Table of Contents