• Reinstallation (FR-A720-1.5K to 90K, FR-A740-2.2K to 132K)
1)After confirming the orientation of the fan, reinstall the fan so that the arrow on the left of "AIR FLOW" faces up.
<Fan side face>
2)Reconnect the fan connectors.
FR-A720-1.5K to 3.7K
FR-A740-2.2K, 3.7K
FR-A720-15K, 18.5K
FR-A740-18.5K, 22K
FR-A720-30K or more
FR-A740-30K to 132K
3) Reinstall the fan cover.
2. Insert hooks until
you hear a click
1. Insert hooks into
sound.
holes.
FR-A720-1.5K to 3.7K
FR-A740-2.2K, 3.7K
CAUTION
Installing the fan in the opposite air flow direction can cause the inverter life to be shorter.
Prevent the cable from being caught when installing a fan.
Switch the power off before replacing fans. Since the inverter circuits are charged with voltage even after power off,
replace fans only when the inverter cover is on the inverter to prevent an electric shock accident.
AIR FLOW
1. Insert hooks into
2. Insert hooks until
holes.
you hear a click
sound.
FR-A720-5.5K to 22K
FR-A740-5.5K to 22K
FR-A720-5.5K to 11K
FR-A740-5.5K to 15K
FR-A720-22K
1. Insert hooks into
holes.
FR-A720-30K or more
FR-A740-30K to 132K
Inspection item
2. Insert hooks until
you hear a click
sound.
411