Setting Procedure Of Real Sensorless Vector Control (Torque Control) - Mitsubishi Electric FR-A720-0.4K Instruction Manual

Fr-a700 series
Hide thumbs Also See for FR-A720-0.4K:
Table of Contents

Advertisement

4.5.2

Setting procedure of real sensorless vector control (torque control)

Set the motor capacity and the number of motor poles. (Pr. 80, Pr. 81)
Select a control method. (Refer to page 91)
Set the torque command. (Pr. 804)
Perform offline auto tuning. (Pr. 96)
As required
⋅ Select online auto tuning. (Pr. 95) (Refer to page 192.)
⋅ Manual input torque control gain adjustment (Refer to page 126)
CAUTION
⋅ Make sure to perform offline auto tuning before performing real sensorless vector control.
⋅ The carrier frequencies are selectable from among 2k, 6k, 10k, 14kHz for real sensorless vector control.
⋅ Torque control can not be performed in the low speed (approx. 10Hz or less) regeneration range and with light load at low speed
(approx. 20% or less of rated torque at approx. 5Hz or less). Choose vector control.
⋅ Performing pre-excitation (LX signal and X13 signal) under torque control may start the motor running at a low speed even when
the start command (STF or STR) is not input. The motor may run also at a low speed when the speed limit value = 0 with a start
command input. Perform pre-excitation after making sure that there will be no problem in safety if the motor runs.
⋅ Do not switch between the STF (forward rotation command) and STR (reverse rotation command) during operation under torque
control. Overcurrent shut-off error (E.OC ) or opposite rotation deceleration error (E.11) occurs.
⋅ For the 0.4K to 3.7K, the speed deviation may become large at 20Hz or less and torque may become insufficient in the low speed
region under 1Hz during continuous operation under real sensorless vector control. In this case, stop the inverter once, then start
(online auto tuning) again to improve.
⋅ When the inverter is likely to start during motor coasting under real sensorless vector control, set to make frequency search of
automatic restart after instantaneous power failure valid (Pr. 57 ≠ "9999", Pr. 162 = "10").
⋅ Enough torque may not be generated in the ultra-low speed range less than approx. 2Hz when performing real sensorless vector
control.
The guideline of speed control range is as shown below.
Driving:
1:200 (2, 4, 6 poles)
1:30 (8, 10 poles)
Regeneration:1:12 (2 to 10 poles) Can be used at 5Hz or more at rated 60Hz
Perform secure wiring.
(Refer to page 14.)
Set the motor. (Pr. 71)
(Refer to page 180.)
Set "3" (standard motor) or "13" (constant torque motor) in Pr. 71
Applied motor.
(Refer to page 91.)
Set the motor capacity (kW) in Pr. 80 Motor capacity and set the
number of motor poles in Pr. 81 Number of motor poles.
(V/F control is performed when the setting is "9999" (initial value).)
Set either "11" (torque control) or "12" (speed-torque switchover) in
Pr. 800 and make torque control valid.
(Refer to page 121.)
Set the speed limit. (Pr. 807)
(Refer to page 123.)
(Refer to page 182.)
Test run
Can be used at 0.3Hz or more at rated 60Hz
Can be used at 2Hz or more at rated 60Hz
Torque control by real sensorless vector
control, vector control
Sensorless
Sensorless
Sensorless
4
119

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents