(9) Setting items and set data
After completion of parameter setting, set the instruction codes and data then start communication from the computer
to allow various types of operation control and monitoring.
Read/
No.
Item
Write
Read
1
Operation mode
Write
Output
frequency/
Read
speed
Output
Read
current
Output
Read
voltage
Special
Read
monitor
Read
Special
monitor
2
selection No.
Write
Alarm
Read
definition
Run command
Write
(extended)
3
Run command
Write
Inverter status
monitor
Read
(extended)
4
Inverter status
Read
monitor
Set frequency
(RAM)
Read
Set frequency
(EEPROM)
Set frequency
5
(RAM)
Write
Set frequency
(RAM, EEPROM)
6
Inverter reset
Write
Alarm definition
7
Write
all clear
Refer to page 320 for data formats (A, A', B, B', C, D)
Instruction
Code
H0000: Network operation
H7B
H0001: External operation
H0002: PU operation
HFB
(RS-485 communication operation via PU connector)
H0000 to HFFFF: Output frequency in 0.01Hz increments
H6F
Speed in 1r/min increments (when Pr. 37 = 1 to 9998 or Pr. 144 = 2 to
10, 102 to 110)
H0000 to HFFFF: Output current (hexadecimal) in 0.01A increments
H70
H71
H0000 to HFFFF: Output voltage (hexadecimal) in 0.1V increments
H72
H0000 to HFFFF: Monitor data selected in instruction code HF3
H73
H01 to H3C: Monitor selection data
Refer to the special monitor No. table (page 327)
HF3
H0000 to HFFFF: Two most recent alarm definitions
H74
H74 to
H75
H77
H76
H77
Refer to the alarm data table (page 328)
HF9
You can set the control input commands such as the forward
rotation signal (STF) and reverse rotation signal (STR). (Refer to
page 328 for details)
HFA
H79
You can monitor the status of the output signals such as forward
rotation, reverse rotation and inverter running (RUN). (Refer to page
329 for details)
H7A
Read the set frequency/speed from the RAM or EEPROM.
H6D
H0000 to HFFFF: Set frequency in 0.01Hz increments
Speed in 1r/min increments (When Pr. 37 = 1 to 9998 or Pr. 144 = 2
H6E
to 10, 102 to 110)
Write the set frequency/speed into the RAM or EEPROM.
HED
H0000 to H9C40 (0 to 400.00Hz) : frequency in 0.01Hz increments
H0000 to H270E (0 to 9998) : speed in r/min increments (when Pr.
37 = 1 to 9998 or Pr. 144 = 2 to 10, 102 to 110)
HEE
⋅ To change the running frequency consecutively, write data to the
inverter RAM. (Instruction code: HED)
H9696: Resets the inverter.
⋅ As the inverter is reset at start of communication by the computer,
the inverter cannot send reply data back to the computer.
HFD
H9966: Resets the inverter.
⋅ When data is sent normally, ACK is returned to the computer and
then the inverter is reset.
HF4
H9696: Alarm history batch clear
Communication operation and setting
Data Description
(55K or less) / 0.1A increments (75K or more)
b15
b8 b7
Second alarm in past
Latest alarm
Fourth alarm in past
Third alarm in past
Sixth alarm in past
Fifth alarm in past
Eighth alarm in past
Seventh alarm in past
Number of
Data Digits
(format)
4 digits
(B.E/D)
4 digits
(A,C/D)
4 digits
(B.E/D)
4 digits
(B.E/D)
4 digits
(B.E/D)
4 digits
(B.E/D)
2digits
(B.E'/D)
2digits
(A',C/D)
b0
4 digits
(B.E/D)
4 digits
(A,C/D)
2digits
(A',C/D)
4 digits
(B.E/D)
2digits
(B.E'/D)
4 digits
(B.E/D)
4 digits
(A,C/D)
4 digits
(A,C/D)
4 digits
(A,D)
4 digits
(A,C/D)