5.1.1

EMC directive

The standards of the EMC Directive are shown below.
Applied
Test standard
standard
EN55011
Radiated noise
EN55011
Conducted noise
EN61000-4-2
Electrostatic immunity
EN61000-4-3
Radiated field AM
modulation
EN61000-4-4
EN61131-2
Fast transient burst
: 2007
*1
noise
EN61000-4-5
Surge immunity
EN61000-4-6
Conducted RF
immunity
5
5.1 Requirements to Meet EMC Directive
- 2
5.1.1 EMC directive
Electromagnetic emissions from the
*1
product are measured.
Electromagnetic emissions from the
product to the power line is
*1
measured.
Immunity test in which static
electricity is applied to the cabinet of
*1
the equipment.
Immunity test in which field is
irradiated to the product.
*1
Immunity test in which burst noise is
applied to the power line and signal
lines.
Immunity test in which lightening
*1
surge is applied to the product.
Immunity test in which a noise
inducted on the power and signal
*1
lines is applied.
Test details
Standard value
30M-230MHz QP:
30dB V/m (30m in measurement
*2, *3
range)
230M-1000MHz QP:
37dB V/m(30m in measurement
*2, *3
range)
150k-500kHz QP:79dB,
*2
Mean: 66dB
500k-30MHz QP:73dB,
*2
Mean: 60dB
4kV Contact discharge
8kV Aerial discharge
80-1000MHz:10V/m
1.4-2GHz:3V/m
2.0-2.7GHz:1V/m
80%AM modulation@1kHz
Power line:2kV
Digital I/O(24V or higher): 1kV
(Digital I/O(24V or less))> 250V
(Analog I/O, signal lines)> 250V
AC power type
Power line (between line and ground)
:
2kV
Power line (between lines)
:
1kV
Data communication port
:
1kV
DC power type
Power line (between line and ground)
:
0.5kV
Power line (between lines)
:
0.5kV
Data communication port
:
1kV
Power line: 10V
Data communication port: 10V