1
3
Check the ionization electrode for signs of wear [2], damage
[3] or contamination [4].
Replace the ionization electrode if necessary.
Close the boiler door as instructed in section 77.
Switch on the power supply to the heating system, see
section 79.
section 108 Checking the ionization circuit;
ground lead
Switch off the power supply to the heating system, see
section 72.
Open the boiler door as instructed in section 73.
1
Check that the ground lead of the ionization circuit [1] has
been installed correctly.
Note: The upper cable is the ground lead of the heat exchanger
pump, the lower cable [1] is the ground lead of the ionization cir-
cuit.
Close the boiler door as instructed in section 77.
Switch on the power supply to the heating system, see
section 79.
Logamax plus GB162-80 kW/100 kW - Subject to modifications resulting from technical improvements!
2
4
section 109 Checking the gas valve;
power supply plug
Switch off the power supply to the heating system, see
section 72.
Open the boiler door as instructed in section 73.
Check that the power supply plug [1] has been attached cor-
rectly to the gas valve.
Close the boiler door as instructed in section 77.
Switch on the power supply to the heating system, see
section 79.
section 110 Checking the gas valve;
activation
Open the boiler door as instructed in section 73.
3
1
Set the multimeter to "Measure AC voltage" [1].
Minimum measuring range 40 VAC.
Put the boiler in flue gas test mode, see section 20.
Check that the gas valve is activated:
[0/l/\|
While operating code
must be available on the two contacts of the right-hand coil
[2] and on the two contacts of the left-hand coil [3] of the gas
valve power supply plug.
Stop the flue gas test as instructed in section 20.
Close the boiler door as instructed in section 77.
Actions
1
2
1
is displayed, approx. 24 VAC
7
79