Disconnect the DHW temperature sensor plug [1].
Set the multimeter to "Measure resistance" [2].
Measure the electrical resistance of the DHW temperature
sensor [3].
Measure the electrical resistance over the DHW temperature
sensor to ground. This electrical resistance must be infinite.
Use a digital contact-type thermometer to measure the tem-
perature in the vicinity of the corresponding sensor.
Compare the resistance values measured at the tempera-
tures measured to the values in section 134.
Replace the relevant sensor if the reading fluctuates by more
than 10 % with respect to the reference value (e.g. infinitely
high resistance in the event of a line break or resistance of
Ω
0
in the case of a short circuit).
Attach the relevant sensor plugs.
Close the boiler door and install the casing of the pump group
in reverse order of removal.
Switch on the power supply to the heating system, see
section 79.
Logamax plus GB162-80 kW/100 kW - Subject to modifications resulting from technical improvements!
2
section 94
Checking the supply, safety, return and DHW
temperature sensors; cables
H
DANGER OF FATAL ACCIDENT
A
due to electric shock!
DAMAGE TO THE INSTALLATION!
To prevent damage, do not insert the multimeter
measuring electrodes too far into the holes of the plug-
and-socket connection.
Switch off the power supply to the heating system, see
section 72.
Open the boiler door as instructed in section 73.
Remove the UBA 3 as instructed in section 82.
Remove the cover from the connection tray, see section 114.
Disconnect the supply temperature sensor plug,
see section 93, [1].
Set the multimeter to "Measure resistance" [1].
Check the supply temperature sensor cable for breaks.
The electrical resistance measured separately for every wire
Ω
must be approx. 0
[2]. Measure between the plug and the
black contacts (low-voltage connector pins 13 and 14) on the
UBA 3 mounting base [3].
Check the supply temperature sensor cable for internal short
circuiting. The electrical resistance, measured between two
random wires, must be infinite.
Measure the electrical resistance over the supply tempera-
ture sensor cable to ground. The electrical resistance must
be infinite for every individual wire.
Disconnect the safety temperature sensor plug as instructed
in section 93, [1].
Actions
81-pin low-voltage connector
16-pin high-voltage connector
3
2
1
7