section 86
Checking and/or replacing the fan unit
H
DANGER OF FATAL ACCIDENT
A
due to electric shock!
DANGER OF FATAL ACCIDENT/FIRE
from explosive fumes.
All work on gas pipes and fittings must be carried out by
authorized gas technicians.
While carrying out these activities check all sealing
rings and gaskets for damage, deformation and signs of
aging and replace if required.
After carrying out these activities, check the system for
leaks on the gas side and/or the flue gas side.
Take the boiler out of operation, see section 72 and 73.
Close the gas stop valve as indicated in section 74.
Remove the power supply plug(s) of the gas regulation
valve [1].
Undo the union from the gas supply [2].
Remove both the fan unit power supply cord plug [1] and the
fan unit tacho cable plug [2].
Logamax plus GB162-80 kW/100 kW - Subject to modifications resulting from technical improvements!
Pull the air suction pipe from the venturi pipe [3].
Open the 4 snap closures of the burner cover.
2
Remove the gas/air unit including the burner cover [1] by
moving it in the direction indicated by the arrow.
1
Actions
7