Vent Termination Clearances - Vermont Castings Stardance 3070 Homeowner's Installation And Operating Manual

Stardance direct vent/natural vent gas heater
Table of Contents

Advertisement

Your stove is approved to be vented either through the
side wall, or vertical through the roof.
Vermont Castings, Majestic Products does not
require any opening for inspection of vent pipe.
Only Vermont Castings, Majestic Products and
Simpson DuraVent venting components specifi-
cally approved and labelled for this stove may be
used.
Minimum clearances between vent pipes and
combustible materials is one (1") inch (25 mm),
except where stated otherwise.
Venting terminals shall not be recessed into a wall or
siding.
Horizontal venting must be installed on a level plane
without an inclining or declining slope.
20003456
Vermont Castings Stardance Direct Vent/Natural Vent Gas Heaterr

Vent Termination Clearances

There must not be any obstruction such as bushes,
garden sheds, fences, decks or utility buildings within
24" from the front of the termination hood.
Do not locate termination hood where excessive snow
or ice build up may occur. Be sure to check vent
termination area after snow falls, and clear to prevent
accidental blockage of venting system. When using
snow blowers, make sure snow is not directed towards
vent termination area.
Location of Vent Termination
It is imperative the vent termination be located observ-
ing the minimum clearances as shown on this page.
9