Abnormal Discharge Pipe Temperature - Daikin Super Multi Plus E-Series Service Manual

Super multi plus e-series
Hide thumbs Also See for Super Multi Plus E-Series:
Table of Contents

Advertisement

Troubleshooting for Outdoor Unit
7.7

Abnormal Discharge Pipe Temperature

F3
Remote Control
Display
Applicable
AII outdoor unit models
Models
Method of
Abnormality is detected according to the temperature detected by the discharge pipe
Malfunction
temperature sensor.
Detection
Malfunction
When the discharge pipe temperature rises to an abnormally high level
When the discharge pipe temperature rises suddenly
Decision
Conditions
Supposed
Causes
Troubleshooting
∗ Refer to "Thermistor Resistance / Temperature Characteristics" table on P407.
368
Faulty discharge pipe temperature sensor
Faulty connection of discharge pipe temperature sensor
Faulty outdoor unit PCB
Be sure to turn off power switch before connect or disconnect connector,
Caution
or parts damage may be occurred.
Discharge
pipe temperature is
120˚C or higher when the
unit stop by
malfunction.
NO
Pull out the discharge pipe
thermistor from the outdoor
PCB, and then make
measurement of resistance
using a multiple meter.
YES
YES
NO
SiEN18-622
Refrigerant shortage, compression
defect, etc. Defect of the refrigerant
system.
Replace the discharge pipe
thermistor.
Replace outdoor unit PC board
(A1P).
(V3068)
Troubleshooting