Daikin Super Multi Plus E-Series Service Manual page 418

Super multi plus e-series
Hide thumbs Also See for Super Multi Plus E-Series:
Table of Contents

Advertisement

Check
Check No. 03
Check for Fan Motor Connector
(1) Turn the power supply off.
(2) With the fan motor connector disconnected, measure the resistance between each pin, then
406
make sure that the resistance is more than the value mentioned in the following table.
1 White
2 Orange
3 Brown
GND
4 Blue
5
6
7 Red
Measurement point
Judgment
1 - 4
1MΩ or more
2 - 4
100kΩ or more
3 - 4
100Ω or more
4 - 7
100kΩ or more
SiEN18-622
Troubleshooting

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents